WAGO-I/O-SYSTEM 750 XTR
Process Image 45
750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR
Manual
Version 1.3.0
Table 35: Modifiable Parameters of the “Settings” Page
Description
Input/Selection
Description
Operating mode
0 mA … 20 mA
Selection of the operating mode
of the I/O module
4 mA … 20 mA
*)
(0)6 V … 18 V
Number format
0 … +65535
*)
Setting of the number notation
−
32768 … +32767
(twos complement)
−
32768 … +32767
(sign + amount)
Output
Output process data
*)
Setting of the switch-on behavior
Output high-
resistance
Switch-on delay after
overtemperature
shutdown
0 ms
Setting of the switch-on delay
100 ms
200 ms
300 ms
500 ms
*)
750 ms
1 sec
2 sec
Maintain limiting
values
OFF
*)
Setting of the overrun limitation
ON
Lower limiting value
0
*)
… +65535
Setting of the lower limiting value
underrange limit (UNR)
Upper limiting value
0 … +65535
*)
Setting of the upper limiting value
overrange limit (OVR)
K-bus timeout
behavior
Keep last output
value
Behavior of the RUN LEDs on
local bus timeout:
RUN LED is always lit
Execute the following
action
*)
Behavior of the RUN LEDs on
local bus timeout:
RUN LED goes out after 100 ms
Timeout action
Output 0 V / 0 A
*)
Local bus timeout behavior
Keep last value
Output high-
resistance
Switch-on value user Substitute value on local bus
timeout
Switch-on value
WAGO
User switch-on value 0
*)
… +65535
Setting the user substitute value
WAGO switch-on
value
0
*)
… +65535
Setting the manufacturer
substitute value
*)
Default setting