WAGO 750-540 Скачать руководство пользователя страница 6

 • 

Important Comments 

 Safety 

Notes

 

  

WAGO-I/O-SYSTEM 

750 

  

I/O 

Modules 

1.4 Safety Notes 

 

Warning

 

Switch off the system prior to working on bus modules! 

In the event of deformed contacts, the module in question is to be replaced, as 
its functionality can no longer be ensured on a long-term basis. 

The components are not resistant against materials having seeping and 
insulating properties. Belonging to this group of materials is: e.g. aerosols, 
silicones, triglycerides (found in some hand creams). 

If it cannot be ruled out that these materials appear in the component 
environment, then additional measures are to be taken:  
- installation of the components into an appropriate enclosure 
- handling of the components only with clean tools and materials. 

 

Attention

 

Cleaning of soiled contacts may only be done with ethyl alcohol and leather 
cloths. Thereby, the ESD information is to be regarded. 

Do not use any contact spray. The spray may impair the functioning of the 
contact area. 

The WAGO-I/O-SYSTEM 750 and its components are an open system. It 
must only be assembled in housings, cabinets or in electrical operation 
rooms. Access must only be given via a key or tool to authorized qualified 
personnel. 

The relevant valid and applicable standards and guidelines concerning the 
installation of switch boxes are to be observed.  

 

ESD

 (Electrostatic Discharge) 

The modules are equipped with electronic components that may be destroyed 
by electrostatic discharge. When handling the modules, ensure that the 
environment (persons, workplace and packing) is well grounded. Avoid 
touching conductive components, e.g. gold contacts. 

 

1.5 Scope 

This manual describes the Digital Output Module 750-540 
4 DO AC 120(230) V 0.25 A, High-Side Switching of the m
odular WAGO-
I/O-SYSTEM 750. 

Handling, assembly and start-up are described in the manual of the Fieldbus 
Coupler. Therefore this documentation is valid only in the connection with the 
appropriate manual. 

Содержание 750-540

Страница 1: ...Fieldbus Independent I O Modules 4 DO AC 120 230 V 0 25 A High Side Switching 750 540 Manual Version 1 0 1...

Страница 2: ...571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be...

Страница 3: ...ion 4 1 1 3 Intended Use 4 1 2 Symbols 5 1 3 Number Notation 5 1 4 Safety Notes 6 1 5 Scope 6 2 I O Modules 7 2 1 Digital Output Module 7 2 1 1 750 540 4 DO AC 120 230 V 0 25 A High Side Switching 7 2...

Страница 4: ...ufacturers are always named without referring to patent rights The existence of such rights can therefore not be ruled out 1 1 2 Personnel Qualification The use of the product detailed in this manual...

Страница 5: ...ation ESD Electrostatic Discharge Warning of damage to the components by electrostatic discharge Observe the precautionary measure for handling components at risk Note Routines or advice for efficient...

Страница 6: ...is to be regarded Do not use any contact spray The spray may impair the functioning of the contact area The WAGO I O SYSTEM 750 and its components are an open system It must only be assembled in hous...

Страница 7: ...2 1 1 750 540 4 DO AC 120 230 V 0 25 A High Side Switching 4 Channel Digital Output Module DC 120 230 V 0 25 A short circuit protected high side switching 2 1 1 1 View 13 14 13 14 C D B A N N N N 750...

Страница 8: ...LEDs An optocoupler is used for electrical isolation between the bus and the field side Any configuration of the output modules is possible when designing the fieldbus node Grouping of module types i...

Страница 9: ...ut DO 1 activated off Output DO 2 not activated green 2 Status DO 2 on Output DO 2 activated off Output DO 3 not activated green 3 Status DO 3 on Output DO 3 activated off Output DO 4 not activated 13...

Страница 10: ...rrent consumption system voltage max 18 mA Voltage via power jumper contacts AC 0 V 230 V 10 Isolation 1 5 kVeff System Supply 2 5 kV rated surge voltage Overvoltage category III Internal bit width 4...

Страница 11: ...provals WAGO I O SYSTEM 750 which you can find on the CD ROM ELECTRONICC Tools and Docs Item No 0888 0412 or in the internet under www wago com Documentation WAGO I O SYSTEM 750 System Description 2 1...

Страница 12: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com...

Отзывы: