290 Appendix
WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V
Manual
Version 1.2.0
Table 69: Register 32
Register 32 – Feature Register
Function
Data Type Access
Factory Setting
Feature Register
Flags
R/W
0x0000
Bit 9: Activation of automatic reset of min/max values for phase 2
0:
Automatic deletion of minimum and maximum current, voltage and power values is
not activated (factory settings).
1:
Automatic deletion of minimum and maximum current, voltage and power values is
activated.
Bit 10: Activation of automatic reset of min/max values for phase 3
0:
Automatic deletion of minimum and maximum current, voltage and power values is
not activated (factory settings).
1:
Automatic deletion of minimum and maximum current, voltage and power values is
activated.
Bit 11: Activation of the Tamper Detect diagnostics
0:
Tamper Detect diagnostics are activated (factory setting).
1:
Tamper Detect diagnostics are deactivated.
Bit 12: User scaling (current converter ratio), phase 1
0:
User scaling is deactivated; the transformation ratio is 1:1 (factory setting).
1:
User scaling is active; the transformation ratio is 1: (divisor for the current
transformer ratio).
Bit 13: User scaling (current transformer ratio), phase 2
0:
User scaling is deactivated; the transformation ratio is 1:1 (factory setting).
1:
User scaling is active; the transformation ratio is 1: (divisor for the current
transformer ratio).
Bit 14: User scaling (current transformer ratio), phase 3
0:
User scaling is deactivated; the transformation ratio is 1:1 (factory setting).
1:
User scaling is active; the transformation ratio is 1: (divisor for the current
transformer ratio).
Bit 15: User scaling (current transformer ratio), neutral conductor
0:
User scaling is deactivated; the transformation ratio is 1:1 (factory setting).
1:
User scaling is active; the transformation ratio is 1: (divisor for the current
transformer ratio).
Table 70: Register 35
Register 35 – Scaling Factor for Energy Values
Function
Data Type Access
Factory Setting
Scaling factor for energy values
UINT
R/W
0x0004
750-495/040-000, 750-495/040-002
750-495/040-001
0:
1 mWh/VARh/VAh
5 mWh/VARh/VAh
1:
0.01 Wh/VARh/VAh
0.05 Wh/VARh/VAh
2:
0.1 Wh/VARh/VAh
0.5 Wh/VARh/VAh
3:
1 Wh/VARh/VAh
5 Wh/VARh/VAh
4:
0.01 kWh/VARh/VAh
0.05 kWh/VARh/VAh
5:
0.1 kWh/VARh/VAh
0.5 kWh/VARh/VAh
6:
1 kWh/VARh/VAh
5 kWh/VARh/VAh
≥
7:
-not permitted-