WAGO I/O System 750 XTR
Process Image 45
750-471/040-000 4AI U/I Diff Galv XTR
Manual
Version 1.0.2
Table 29: Signal Types “0 … 10 V, 0 … 20 mA” and “4 … 20 mA” with Status Information in the
Process Image
Measuring range
Process value
Status
byte
hex.
Error
LED
0 … 10 V
0 …
20 mA 4 … 20 mA
Binary
Hex.
Dec.
Measuring value XFÜ
1)
n.a.
<
−
22.0
<
−
14.0
0000.0000.0000.0 011
0x0003
3
0x50
on
Neg. sensor overload
3)
n.a.
n.a.
< 1.0
0000.0000.0000.0 011
0x0003
3
0x60
on
Wire break
3)
<
−
0.5
<
−
1.0
< 3.0
0000.0000.0000.0 011
0x0003
3
0x41
on
Underrange
2)
0
0
4.0
0000.0000.0000.0 000
0x0000
0
0x00
off
1
2
5.6
0000.1100.1100.0 000 0x0CC8 3272
0x00
off
2
4
7.2
0001.1001.1001.1 000
0x1998 6552
0x00
off
3
6
8.8
0010.0110.0110.0 000
0x2660 9824
0x00
off
4
8
10.4
0011.0011.0011.0 000
0x3330 13104
0x00
off
5
10
12.0
0011.1111.1111.1 000
0x3FF8 16376
0x00
off
6
12
13.6
0100.1100.1100.1 000 0x4CC8 19656
0x00
off
7
14
15.2
0101.1001.1001.1 000
0x5998 22936
0x00
off
8
16
16.8
0110.0110.0110.0 000
0x6660 26208
0x00
off
9
18
18.4
0111.0011.0011.0 000
0x7330 29488
0x00
off
10
20
20.0
0111.1111.1111.1 000
0x7FF8 32760
0x00
off
Exceeding
2)
0111.1111.1111.1 011 0x7FFB 32763
0x42
on
> 10.4
> 21.0
> 21.0
Sensor overload
3)
0111.1111.1111.1 011 0x7FFB 32763
0x50
on
n.a.
> 22.0
> 22.0
1)
Status bits: X: not used, F= error, Ü= overrange
2)
When underrange / overrange limit is ON
3)
When wire break / overload diagnostics is ON