Table 28: Process Image Type N, With Wire Break Diagnostics
Temperature
°C
Numeric value
1)
Status
byte
hex.
LED
error
AI 1, 2
Binary
Hex.
Dec.
< −100.0
’1111 1100 0001 1000’
0xFC18
−1000
0x41
ON
−100
’1111 1100 0001 1000’
0xFC18
−1000
0x00
OFF
0
’0000 0000 0000 0000’
0x0000
0
0x00
OFF
100
’0000 0011 1110 1000’
0x03E8
1000
0x00
OFF
200
’0000 0111 1101 0000’
0x07D0
2000
0x00
OFF
300
’0000 1011 1011 1000’
0x0BB8
3000
0x00
OFF
400
’0000 1111 1010 0000’
0x0FA0
4000
0x00
OFF
500
’0001 0011 1000 1000’
0x1388
5000
0x00
OFF
1000
’0010 0111 0001 0000’
0x2710
10000
0x00
OFF
1200
’0010 1110 1110 0000’
0x2EE0
12000
0x00
OFF
1300
’0011 0010 1100 1000’
0x32C8
13000
0x00
OFF
approx. 1300
’0011 0010 1100 1000’
> 0x32C8
> 13000
0x42
ON
Wire break
’0111 1111 1111 1111’
0x7FFF
32767
0x42
ON
1)
Temperature values below 0 °C are represented in two's complement binary.
Table 29: Process Image Type U, With Wire Break Diagnostics
Temperature
°C
Numeric value
1)
Status
byte
hex.
LED
error
AI 1, 2
Binary
Hex.
Dec.
<
−25.0
’1111 1111 1110 0111’
< 0xFFE7
<
−250
0x41
ON
−25
’1111 1111 1110 0111’
0xFFE7
−250
0x00
OFF
0
’0000 0000 0000 0000’
0x0000
0
0x00
OFF
100
’0000 0011 1110 1000’
0x03E8
1000
0x00
OFF
200
’0000 0111 1101 0000’
0x07D0
2000
0x00
OFF
300
’0000 1011 1011 1000’
0x0BB8
3000
0x00
OFF
400
’0000 1111 1010 0000’
0x0FA0
4000
0x00
OFF
500
’0001 0011 1000 1000’
0x1388
5000
0x00
OFF
600
’0001 0111 0111 0000’
0x1770
6000
0x00
OFF
approx. 600.0
’0001 0111 0111 0000’
> 0x1770
> 6000
0x42
ON
Wire break
’0111 1111 1111 1111’
0x7FFF
32767
0x42
ON
1)
Temperature values below 0 °C are represented in two's complement binary.