10 •
750-454 [2 AI 4-20 mA, Differential Inputs]
Technical Data
WAGO-I/O-SYSTEM
750
I/O
Modules
2.1.1.6 Technical Data
Module Specific Data
Number of inputs
2
Voltage supply
via system voltage DC /DC
Current consumption
typ.
(internal)
70 mA
Common mode voltage
max.
35
V
Signal current
4 mA... 20 mA
Input resistance
<220
Ω
at 20 mA
Resolution 12
bits
Conversion time
typ.
2
ms
Measuring error
25°C
<
±
0,2 % of full scale value
Temperature coefficient
<
±
0,01 % /K of full scale value
Isolation
500 V (Field/System)
Bit width
2 x 16 bits data
2 x 8 bits control/status (option)
Dimensions (mm) W x H x L
12 x 64* x 100
* from upper edge of 35 DIN rail
Weight
ca. 55 g
Standards and Regulations (cf. Chapter 2.2 of the Coupler/Controller Manual)
EMC-Immunity to interference (CE)
acc. to EN 50082-2 (96)
EMC-Emission of interference (CE)
acc. to EN 50081-1 (93)
EMC-Immunity to interference
(Ship building)
acc. to Germanischer Lloyd (97)
EMC-Emission of interference
(Ship building)
acc. to Germanischer Lloyd (97)