background image

8  •

 

750-405 [2 DI AC 230 V 10 ms, High-Side Switching] 
Display Elements 

  

WAGO-I/O-SYSTEM 

750 

  

I/O 

Modules 

 

Attention 

An additional supply module must be added for the field supply with AC 
230 V! 

The supply voltage for the field side is made automatically through the 
individual I/O modules by means of power jumper contacts. 

 

Warning 

The maximum current of the internal power jumper contacts is 10 A. When 
configuring the system it is important not to exceed the maximum/sum 
current. However, if such a case should occur, another supply module must be 
added. 

The digital input module 750-405 can be used with all couplers/controllers of 
the WAGO-I/O-SYSTEM 750. 

2.1.1.3 Display 

Elements 

LED 

Channel  Designation  State  Function

 

off 

Input DI 1: Signal voltage (0) 


green 

Status 

DI 1 

on 

Input DI 1: Signal voltage (1) 

off 

Input DI 2: Signal voltage (0) 

13 14

C

D

B

A

C

A

 

Fig. 2.1.1-2: Display 
Elements

 g040002x

 


green 

Status 

DI 2 

on 

Input DI 2: Signal voltage (1) 

 

Содержание 750-405

Страница 1: ...Fieldbus Independent I O Modules 2 DI AC 230 V 10 ms High Side Switching 750 405 Manual Version 1 0 5 ...

Страница 2: ...0 571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be fully ex cluded we would appreciate any information or ideas at any time E Mail documentation wago com We wish to point out that the software and hardware terms as well as the trademarks of companie...

Страница 3: ...ication 4 1 1 3 Intended Use 4 1 2 Symbols 5 1 3 Number Notation 5 1 4 Safety Notes 6 1 5 Scope 6 2 I O Modules 7 2 1 Digital Input Modules 7 2 1 1 750 405 2 DI AC 230 V 10 ms High Side Switching 7 2 1 1 1 View 7 2 1 1 2 Description 7 2 1 1 3 Display Elements 8 2 1 1 4 Schematic Diagram 9 2 1 1 5 Technical Data 10 2 1 1 6 Process image 11 ...

Страница 4: ...nufacturers are always named without referring to patent rights The existence of such rights can therefore not be ruled out 1 1 2 Personnel Qualification The use of the product detailed in this manual is exclusively geared to specialists having qualifications in PLC programming electrical specialists or persons instructed by electrical specialists who are also familiar with the valid standards WAG...

Страница 5: ...ration ESD Electrostatic Discharge Warning of damage to the components by electrostatic discharge Observe the precautionary measure for handling components at risk Note Routines or advice for efficient use of the device and software optimization More information References on additional literature manuals data sheets and INTERNET pages 1 3 Number Notation Number Code Example Note Decimal 100 norma...

Страница 6: ...tion is to be regarded Do not use any contact spray The spray may impair the functioning of the contact area The WAGO I O SYSTEM 750 and its components are an open system It must only be assembled in housings cabinets or in electrical operation rooms Access must only be given via a key or tool to authorized qualified personnel The relevant valid and applicable standards and guidelines concerning t...

Страница 7: ...eives control signals from digital field devices sensors switches etc The module is a 2 to 4 conductor device and has two input channels Two sensors may be directly connected to the module Two 4 conductor sensors with ground earth wire may be directly connected to 230 V N PE earth potential and signal input DI 1 or signal input DI 2 Each input module has an RC noise rejection filter with a time co...

Страница 8: ...umper contacts is 10 A When configuring the system it is important not to exceed the maximum sum current However if such a case should occur another supply module must be added The digital input module 750 405 can be used with all couplers controllers of the WAGO I O SYSTEM 750 2 1 1 3 Display Elements LED Channel Designation State Function off Input DI 1 Signal voltage 0 A green 1 Status DI 1 on ...

Страница 9: ... AC 230 V 10 ms High Side Switching 9 Schematic Diagram WAGO I O SYSTEM 750 I O Modules 2 1 1 4 Schematic Diagram DI 1 DI 2 230V N DI 230V DI 100nF U N 1 2 3 4 5 6 7 8 750 405 Fig 2 1 1 3 Schematic Diagram g040501e ...

Страница 10: ...Nom 10 50 Hz 10 60 Hz 10 Isolation 1 5 KVeff System Field 2 5 kV Impulse voltage withstand level Overvoltage category III Internal bit width 2 Bit Dimensions W x H x L from upper edge of 35 DIN rail 12 mm x 64 mm x 100 mm Weight ca 50 g Standards and Regulations cf Chapter 2 2 of the Coupler Controller Manual EMC Immunity to interference CE acc to EN 50082 2 96 EMC Emission of interference CE acc ...

Страница 11: ...2 3 4 NKK Nippon Kaiji Kyokai RINA Registro Italiano Navale CULUS UL1604 Class I Div2 ABCD T4A KEMA II 3 G EEx nA II T4 Conformity Marking More Information Detailed references to the approvals are listed in the document Overview Approvals WAGO I O SYSTEM 750 which you can find on the CD ROM ELECTRONICC Tools and Docs Item No 0888 0412 or in the internet under www wago com Æ Documentation Æ WAGO I ...

Страница 12: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastraße 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com ...