8 •
750-405 [2 DI AC 230 V 10 ms, High-Side Switching]
Display Elements
WAGO-I/O-SYSTEM
750
I/O
Modules
Attention
An additional supply module must be added for the field supply with AC
230 V!
The supply voltage for the field side is made automatically through the
individual I/O modules by means of power jumper contacts.
Warning
The maximum current of the internal power jumper contacts is 10 A. When
configuring the system it is important not to exceed the maximum/sum
current. However, if such a case should occur, another supply module must be
added.
The digital input module 750-405 can be used with all couplers/controllers of
the WAGO-I/O-SYSTEM 750.
2.1.1.3 Display
Elements
LED
Channel Designation State Function
off
Input DI 1: Signal voltage (0)
A
green
1
Status
DI 1
on
Input DI 1: Signal voltage (1)
off
Input DI 2: Signal voltage (0)
13 14
C
D
B
A
C
A
Fig. 2.1.1-2: Display
Elements
g040002x
C
green
2
Status
DI 2
on
Input DI 2: Signal voltage (1)