180 Appendix
WAGO I/O SYSTEM 750 XTR
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
The following table describes the process image information, e.g., allocation of
configuration modules, for the AS interface master module. All other possible
process image assignments are available in the AS interface master module
manual.
Table 123: AS Interface Master
– Process Image Information
PBDP module type
PI
Offset
[Byte]
Bit/byte allocation
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
ASI_10D
I
0
PD
RA
F
0
Status 0 / Register RES
Channel 0 / Table 0
1
2
Receive data
Mailbox Byte 0
Register data RD
Table 0, LB
3
Receive data
Mailbox Byte 1
Register data RD
Table 0, HB
4
Receive data
Mailbox Byte 2
5
Receive data
Mailbox Byte 3
6
Receive data
Mailbox Byte 4
7
Receive data
Mailbox Byte 5
8
Input data
ASi-Master Flags
Input data
ASi-Slave 1/1A
9
Input data
ASi-Slave 2/2A
Input data
ASi-Slave 3/3A
10
Input data
ASi-Slave 4/4A
Input data
ASi-Slave 5/5A
11
Input data
ASi-Slave 6/6A
Input data
ASi-Slave 7/7A
ASI_18D
…
…
…
19
Input data
ASi-Slave 22/22A
Input data
ASi-Slave 23/23A
ASI_22D
…
…
…
23
Input data
ASi-Slave 30/30A
Input data
ASi-Slave 31/31A
ASI_30D
…
…
…
31
Input data
ASi-Slave 14B
Input data
ASi-Slave 15B
ASI_38D
…
…
…
39
Input data
ASi-Slave 30B
Input data
ASi-Slave 31B
ASI_46D
…
…
…
47
Input data
---
Input data
---