WAGO I/O System 750
Device Description 19
750-1505 16DO 24VDC 0.5 A, low-side switching
Manual
Version 1.1.0
Public
Pos: 28 /Serie 750 ( WAGO I/O SYSTEM)/Ger ätebeschrei bung (al te Str uktur)/Anschlüsse/Leistungskontakte/F eldversorgung - Überschrift 3 @ 6\mod_1256294692864_21.docx @ 43664 @ 3 @ 1
3.2.2
Power Jumper Contacts/Field Supply
Pos: 29.1 /Serie 750 (WAGO I/O SYSTEM)/Wichtige Erläuterungen (al te Str uktur)/Sicherheits- und sonstige Hinweise/Vorsicht/Vorsicht: Verletzungsgefahr durch scharfkantige M esser kontakte! @ 6\mod_1256193279401_21.docx @ 43414 @ @ 1
Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury. Do not touch the blade contacts.
Pos: 29.2 /Serie 750 (WAGO I/O SYSTEM)/Ger ätebeschrei bung (al te Str uktur)/Anschlüsse/Leistungskontakte 2 LK (Messer/F eder) - Einl eitung @ 15\mod_1371721641099_21.docx @ 123714 @ @ 1
The I/O module 750-1505 has 2 self-cleaning power jumper contacts that supply
and transmit power for the field side. The contacts on the left side of the I/O
module are designed as blade contacts and those on the right side as spring
contacts.
Pos: 29.3 /Serie 750 (WAGO I/O SYSTEM)/Ger ätebeschrei bung (al te Str uktur)/Anschlüsse/Leistungskontakte 2 LK (Messer/F eder) - Abbildung ( 16- Kanal) @ 15\mod_1370866610582_21.docx @ 122222 @ @ 1
Figure 3: Power Jumper Contacts
Pos: 29.4 /Serie 750 (WAGO I/O SYSTEM)/Ger ätebeschrei bung (al te Str uktur)/Anschlüsse/Leistungskontakte 2 LK (Messer/F eder) - Leg ende @ 15\mod_1371721352500_21.docx @ 123710 @ @ 1
Table 4: Legend for Figure “Power Jumper Contacts”
Contact
Type
Function
1
Spring contact Potential transmission (U
v
) for field supply
2
Spring contact Potential transmission (0 V) for field supply
3
Blade contact Potential feed-in (0 V) for field supply
4
Blade contact Potential feed-in (U
v
) for field supply
Pos: 29.5 /Serie 750 (WAGO I/O SYSTEM)/Wichtige Erläuterungen (al te Str uktur)/Sicherheits- und sonstige Hinweise/Achtung/Achtung: M axi mal er Strom Leistungskontakte 10 A @ 3\mod_1226499143500_21.docx @ 25029 @ @ 1
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.
Pos: 29.6 /Serie 750 (WAGO I/O SYSTEM)/Wichtige Erläuterungen (al te Str uktur)/Sicherheits- und sonstige Hinweise/Hinweis/Hi nweis: Potenti alei nspeisemodul für Er de ei nsetzen! ( keine LK für Er de) @ 3\mod_1226499037468_21.docx @ 25023 @ @ 1