750-1423 4DI 24V DC 2.0ms, low-side switching, 3-conductor
Manual
Version 1.2.0
3.6.5
Connection Type
Table 11: Technical Data
‒ Field Wiring
Wire connection
Push-in CAGE CLAMP
®
Cross section, solid wire
0.08 mm² …
1.5 mm² / AWG 28
… 16
Cross section, fine-stranded wire
0.25 mm² …
1.5 mm² / AWG 22
… 16
Stripped lengths
8 mm
…
9 mm / 0.33 in
Table 12: Technical Data – Power Jumper Contacts
Power jumper contacts
Blade/spring contact, self-cleaning
Table 13: Technical Data – Data Contacts
Data contacts
Slide contact, hard gold plated, self-
cleaning
3.6.6
Climatic Environmental Conditions
Table 14: Technical Data – Climatic Environmental Conditions
Operating temperature range
0 °C
…
55 °C
Storage temperature range
−
25 °C
…
+85 °C
Relative humidity without condensation Max. 95
%
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75
%
SO
2
≤
25 ppm
H
2
S
≤
10 ppm
Special conditions
Ensure that additional measures for
components are taken, which are used in
an environment involving:
– dust, caustic vapors or gases
– ionizing radiation