787-1226
Properties
18
Product manual | Version: 1.0.0
Compact Power Supply
Table 15: Technical Data – Output
Property
Value
Output voltage range
22 … 27 VDC
Factory Settings
24 VDC; ±1 %
Output Current
4.8 A (at 100 … 240 VAC), 6.0 A (at 110 … 240
VAC)
Output Power
120 W (at 100 … 240 VAC), 150 W (at 110 …
240 VAC)
Power factor
1)
> 0.65
Capacitive load (max.)
1)
110 VAC
> 40000 µF
230 VAC
> 40000 µF
Capacitive load (max.)
2)
110 VAC
> 50000 µF
230 VAC
> 50000 µF
Voltage variation
±1 % (at 100 … 240 VAC)
Derating of output power
For high surrounding air temperatures, see
Line regulation
1
±1 %
Load regulation
3)
±1 %
Residual ripple/noise
< 100 mV (at 100 … 240 VAC)
Overload behavior
4)
(1.05–1.35) × IOUT: Power limitation; shutdown
in the event of a short circuit and permanent
overload
Short-circuit condition: Hiccup mode
5)
Switch-on delay
6)
110 VAC
< 600 ms
1)
230 VAC
< 400 ms
1)
1
At nominal load
2)
At 50 % nominal load
3)
0 % / 100 % load step
4)
See “Overload Behavior” Figure
5)
See “Hiccup Mode” Figure; t
on
= 150 ms / t
off
= 1700 ms
6)
See “Switch-on Time” Figure
100%
105%
135%
140%
160%
Constant
Power Mode
24
(VDC)
0
OUT
normal
I
Overload Mode
(105 % up to 135 %)
Constant Power Mode
Short Circuit Protection
(140 % up to 160 %)
Auto Recovery
OUT
U
OUT
(ADC)
I
Figure 9: Overload Behavior