2789-9080
Fieldbus Description
18
| Version: 1.1.0
Communication Module IO-Link
4.2.2 Specific Module Parameters of the WAGO Power Supply Pro 2
The product uses the following WAGO-specific parameters:
Table 15: WAGO-specific parameters
Index
Subindex
Parameters
Data Type
Data length
(Bytes)
Description
12001
0
Part number
module
StringT
8
Module item
number
12002
0
Part number ex-
tension (module)
StringT
8
Item number ex-
tension of the
module
12003
0
Hardware version
module
StringT
2
HW Release In-
dex of the mod-
ule in the "XX"
format
12004
0
Firmware version
module
StringT
8
FW Revision of
the module in the
"XX.XX.XX" for-
mat
12005
0
Configuration ID
module
UIntegerT
4
Configuration ID
of the module
4.2.3 Data Structure for WAGO Power Supplies Pro 2
The product has the following structure:
• 5-byte input process data
• 1-byte output process data
The structure of the input and output process data is explained below.
Input Process Data
The product has the following input process data (5 bytes):
Table 16: Process Data Structure
Byte
Description
0
Status messages (see Table “Status Message Structure”)
1 … 2
Measured output current 0.000 … 65.535 A in steps of 1 mA
3 … 4
Measured output voltage 0.000 … 65.535 V insteps of 1 mV
Table 17: Status Message Structure
Bit
Description
0
DC OK
Set when the output voltage is OK.
1
Overtemperature shutdown T ≥ T
max
2
No output voltage
3
Short circuit at output
4
Digital output set
5 … 7
Reserved
Output Process Data
The product has the following output process data (1 byte):