2789-9023
Fieldbus Description
34
Product manual | Version: 1.0.0
EtherNet/IP Communication Module
DC Output
Table 31: Parameters – DC Output
Attribute ID
Access
Data type
Description
136
Get/Set
UINT16
Output voltage (unit: mV)
137
Get/Set
UINT16
Warning threshold (unit: mA)
138
Get/Set
UINT16
Bit 0
Switch output on
Bit 1
“Active droop” parallel switching mode
Bit 2
Overload threshold enabled
Bit 3
Enable switching the DC output on and off
via cyclic process data
Bits 4 … 5 Reserved
Bit 6
1
Constant current
Bit 7
1
Constant current with latching shutdown
Bit 8
1
Hiccup mode
Bit 9
1
Electronic circuit breaker
Bits 10 …
11
Reserved
Bit 12
Latching shutdown on thermal overload
Bit 13
PowerBoost
Bit 14
TopBoost
Bit 15
Reserved
139
Get/Set
UINT16
Switch-on delay (unit: ms)
1 At least one bit must be set, and the bits are mutually locked.
Electronic Circuit Breaker Mode
Table 32: Parameters – Electronic Circuit Breaker Mode
Attribute ID
Access
Data type
Description
148
Get/Set
UINT16
Trip current (unit: mA)
149
Get/Set
UINT16
Trip delay (unit: ms)
Signaling – Digital Input
Table 33: Parameter – Signaling – Digital Input
Attribute ID
Access
Data type
Description
168
Get/Set
UINT16
Bit 0
Switch power supply on and off
Bits 1 … 9
Reserved
Bit 10
1
Inversion
Bit 11
1
Function on edge change (0 to 1)
Bit 12
1
Function on edge change (1 to 0)
Bits 13 … 15 Reserved
1 All bits can be 0 and are mutually locked.
Signaling – Digital Output
Table 34: Parameter – Signaling – Digital Output
Attribute ID
Access
Data type
Description
176
Get/Set
UINT16
Bit 0
DC status OK
Bit 1
Overload threshold exceeded
Bit 2
Electronic circuit breaker tripped
Bit 3
Latching shutdown occurs