2787-2448
Properties
Product manual | Version: 1.0.0
23
Power Supply Pro 2
Table 24: Technical Data – Signal Connection
Property
Value
Specifications of the conductors used
≥ +75 °C/167 °F (ambient air temperature: ≤ +60
°C/140 °F)
≥ +90 °C/194 °F (ambient air temperature: > +60
°C/140 °F)
Required tools (conductor termination)
Operating tool, with a partially insulated shaft,
type 2 (see section
8
3.9.6 Communication
Table 25: Technical Data – Communication
Property
Value
Data timeliness of the communication interface
200 ms
3.9.7 MTBF/Lifespan
Table 26: Technical Data – MTBF/Lifespan
Property
At
Load
T
amb
Value
MTBF, typ. (SN 29500) (IEC 61709)
24 VDC
100 %
25 °C
920000 h
24 VDC
100 %
40 °C
550000 h
3.9.8 Environmental Conditions
Table 27: Technical Data ‒ Environmental Conditions
Property
Value
Surrounding air temperature, operation
−25 … +70 °C
Surrounding air temperature, restricted operation
1)
−40 … −25 °C
Surrounding air temperature, storage
−40 … +85 °C
Derating (temperature-dependent)
2)
−3 %/K (> +55 °C)
Derating (location-dependent)
2)
−8.9 %/1000 m (> +50 °C; 3600 m or higher)
−8.6 %/1000 m (> +55 °C; 2100 m or higher)
Relative humidity
5 … 96 % (no condensation permissible)
Elevation above sea level, max.
5000 m
Overvoltage category
III (≤ 2000 m)
II (> 2000 m)
Vibration according to IEC 60068-2-6
5 … 150 Hz / 1g
Shock according to IEC 60068-2-27
15g / 11 ms
Pollution degree according to IEC/EN 60664-1
2
1)
Without mechanical actuation of buttons, female connectors etc., for example
2)
See section
8
Note
Observe the following for long-term storage:
For long-term storage, power must be applied to equipment with built-in capacitors for
five minutes at least every two years.
3.9.9 Product Protection
Table 28: Technical Data – Product Protection
Property
Value
Internal input fuse
1)
T 10 A / 250 VAC
Transient suppression at input
Yes, varistor