11

Elite 2000W—Pure Sine Inverter 

by Wagan Tech

©2010 Wagan Corporation

All Rights Reserved

Wagan and wagan.com are trademarks used by Wagan Corporation

12

User’s Manual—Read before using this equipment

DC Cable Gauge 

Minimize cable losses by using the thickest wire available and the shortest 
practical length. 

Measure Round Trip (RT) cable distances in feet. Round Trip cable distance is 
battery to inverter and back to battery. If the application is in a vehicle with 
engine operating, use the supplied cables for round trip distances up to 5 feet.

Use a recommended ANL fuse and Fuse holder. Fuse at  300 Amps. ANL are 
quick acting and sealed so they do not spark when they blow. Place fuse no 
more than one foot from the Positive (+) terminal of the battery.

RT Length 

4-6 Ft

7-8 Ft

9-10 Ft

11-14 Ft

AWG

2

0

0

0

If the inverter and the battery are positioned within 4 feet of each other, 
a minimum of 4 AWG insulated copper wire should be used to make the 
connections. If the distance is longer than 32 inches (2.6 ft), heavier wire will 
be required. 

The cables that are supplied with the inverter can be used for full wattage 
applications that have the batteries under constant or frequent charge (mobile 
applications). The supplied cable has an electrically equivalent 300 Amp ANL 
fuse attached.

Connecting the Inverter 

Loose connections will result in a severe voltage drop that can cause damage 
to connectors, conductors, and insulation and can cause sparking. Reverse 
polarity connection will blow the fuses in the inverter and can permanently 
damage to the inverter. Damage caused by reverse polarity will void the 
warranty. 

Installation Procedure 

1.  Mount the inverter in a secure location. If the inverter is to be mounted 

on a wall, mount it horizontally. Make sure that the front and rear of the 
inverter has free air flow.

2.  Make sure the cables are the proper gauge and have the fuse holder as 

close to the battery bank’s Positive (+) terminal as possible.

3.  Install the fuse in the Positive (+) cable. 
4.  Make sure the ON/OFF switch located on the front panel of the inverter  

is in the OFF (0) position. 

5.  Locate the ground lug terminal on the inverter. Connect an insulated 10 

gauge copper wire to the terminal. The other end of the ground wire is 
connected to a “proper” grounding point. Use the shortest practical length 
of wire. Connect this wire to the chassis of your vehicle or to the grounding 
system in your boat. In a city, the ground wire can connect to a metal cold 
water pipe that goes underground. In remote locations, the ground wire 
can be connected to an “earth ground”. This can be an attachment to a 
foot long copper clad metal rod driven into the ground. In the unlikely 
event of a short circuit, operating the inverter without proper grounding 
can result in electrical shock. Do not directly connect this ground wire to 
the Negative (-) DC Terminal of the inverter. As an alternative grounding 
connection, use the Negative (-) terminal of the battery. 
NOTE: Crimp-on ring terminals are required on all cable ends. The cable 
ends need to be stripped of insulation for 1/2 inch before crimping on ring 
terminals. Select a crimp terminal size to fit the gauge cable and inverter 
and battery terminal connectors. After crimping make sure that the cable 
connectors are secure on the cables so there are no loose connections. 

6.  Connect the Negative (-) cable end to the inverter terminal and battery 

Negative Terminal. Make sure you have good, secure connections. 

7.  Recheck and make sure the DC cable fuse is installed in the fuse holder. 

CAUTION: Making an initial connection between the positive cable end 
and the inverter’s positive terminal may cause a spark. This is a normal  
and is a result of capacitors in the inverter starting to charge. Because of 
the possibility of sparking, it is extremely important that both the inverter 
and the battery bank be positioned away from any source of flammable 
fumes or gases. Failure to heed this warning can result in fire or explo-
sion. Do not make the positive terminal connection immediately after the 
batteries have been charging. Allow time for the battery gasses to vent to 
outside air. 

Содержание 2205

Страница 1: ...item 2205 User s Manual SHEMO080100244TXC ...

Страница 2: ...ing this inverter Keep this manual for future use About This Inverter This power inverter converts 12 volts direct current 12V DC to 120 volts alternating household current 120V AC It easily powers TV VCR combinations small microwave ovens and refrigerators It also operates at high efficiency up to 90 that results in long running time and extended battery life compared to other inverters with this...

Страница 3: ...e Digital Display Shows the DC Voltage input that the inverter senses at its terminals Low battery excessive load for the cables can cause a low voltage reading and inverter shutdown Low battery is also indicated when the Audible Alarm sounds An alternative display shows the Percent of Load that the inverter can handle If the inverter has excessive load OVL will be displayed Audible Alarm internal...

Страница 4: ...the inverter Off momentarily press Lock If the wireless remote fails to control operation of the inverter you may be out of range for the radio signal move closer to the inverter If the Remote Switch has a depleted battery open the unit by unscrewing the three small screws on the back side of the remote control and replace the 12 volt model 23A alkaline battery with a new one Rear Panel Positive T...

Страница 5: ...his is done by multiplying average power consumption in watts by hours of run time For example 500 watts for 10 hours 5000 watt hours To get an estimate of the maximum current in amps that a battery bank must be capable of delivering to the inverter divide the load watts by ten For example a 500 watt appliance load will need 50 amps at 12 volts DC Using the 500 watts or 50 amps for 10 Load Conside...

Страница 6: ...age of a nominal 12 volt battery starts at 13 4 volts fully charged then drops to 10 5 volts discharged If the load on the battery causes the battery to discharge faster than the 20 hour rate the capacity AH of the battery is measurably reduced derated In heavy battery discharge applications double the estimated Amp Hour rating and configure batteries to support this capacity If the batteries are ...

Страница 7: ...ble 3 Install the fuse in the Positive cable 4 Make sure the ON OFF switch located on the front panel of the inverter is in the OFF 0 position 5 Locate the ground lug terminal on the inverter Connect an insulated 10 gauge copper wire to the terminal The other end of the ground wire is connected to a proper grounding point Use the shortest practical length of wire Connect this wire to the chassis o...

Страница 8: ...h either wind power or solar power These can continue to operate during power outages and they also reduce recharge time For mobile or marine charging systems a higher rated alternator may be necessary to charge a battery bank Regular Loss of Commercial Power If the inverter system is used during commercial power outages that occur daily configure the charger system to replace energy during the ti...

Страница 9: ...hut down mode Allow inverter to cool Check for adequate ventilation Reduce the load on the inverter to rated continuous power output Unit may be defective See warranty and call customer service PROBLEM Inverter Shut Down Fault LED Lit OVL Display Reason Solution Equipment being operated draws too much power Use a higher capacity inverter or do not use this equipment PROBLEM Continuous Buzzing Soun...

Страница 10: ...rized personnel or other causes not arising out of defects in materials or workmanship This warranty is effective only if the product is purchased and operated in the USA and does not extend to any units which have been used in violation of written instructions furnished Warranty Disclaimers This warranty is in lieu of all warranties expressed or implied and no representative or person is authoriz...

Страница 11: ...customerservice wagan com Toll Free 1 800 231 5806 31088 San Clemente Street Hayward CA 94544 U S A 2010 Wagan Corporation All Rights Reserved Wagan and wagan com are trademarks used by Wagan Corporation REV20100927 ...

Отзывы: