4.4

Generator Derating

All generators are subject to derating for altitude and temperature.
Internal combustion engines, unless modified, run less efficiently at
higher altitudes due to the reduction of air pressure. This translates
into a lack of power and thus reduction in generator output.
Temperature affects both engine and generator performance. As
temperature increases, an engine will run less efficiently and more
resistance will be found in electrical components. Therefore, as the
temperature increases, the output of the generator decreases. Altitude
also affects the cooling capacity of air—the higher the altitude the less
dense the air is and thus the lower its ability to transfer heat.

For every increase in altitude of 500 m (1650 ft.) above 1000 m (3300
ft.), the output of the generator will be reduced by 3%. For every
increase of 5° C (9° F) in ambient temperature above 40° C (104° F),
the output of the generator will be reduced by 3%. Use the tables
shown for altitude and temperature deration factors. It may be
necessary to consider both altitude and ambient temperature deration
factors to determine true generator output.

Ambient Temp.

°C (°F)

Derate

Factor

45 (113)

3 %

0.97

50 (122)

6 %

0.94

55 (131)

9 %

0.91

60 (140)

12 %

0.88

Altitude

m (ft.)

Derate

Factor

1500 (4900)

3 %

0.97

2000 (6600)

6 %

0.94

2500 (8200)

9 %

0.91

3000 (9900)

12 %

0.88

3500 (11500)

15 %

0.85

4000 (13100)

18 %

0.82

Содержание GV 7000A

Страница 1: ...www wackergroup com Generator GV 7000A GV 7003A OPERATOR S MANUAL 0157387en 004 1106 0 1 5 7 3 8 7 E N...

Страница 2: ...enclosed areas Deadly levels of carbon monoxide can build up in these areas Using a fan or opening windows and doors does NOT supply enough fresh air ONLY use a generator outside and far away from wi...

Страница 3: ...ns 8 2 5 Safety and Operating Labels 9 3 Technical Data 11 3 1 Generator 11 3 2 Engine 13 3 3 Sound Specifications 13 4 Operation 14 4 1 Determining Power Requirements 14 4 2 Outdoor Installation 16 4...

Страница 4: ...25 5 1 Engine Maintenance 25 5 2 Periodic Maintenance Schedule 25 5 3 Engine Oil 26 5 4 Air Cleaner 27 5 5 Spark Plug 28 5 6 Engine Speed 29 5 7 Storage 30 5 8 Transport 30 5 9 Troubleshooting 31 5 1...

Страница 5: ...ment please contact Wacker Corporation The information contained in this manual was based on machines in production at the time of publication Wacker Corporation reserves the right to change any porti...

Страница 6: ...his symbol to avoid possible injury or death DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avo...

Страница 7: ...uctions contained in both this manual and the engine manual and familiarize yourself with the location and proper use of all controls Inexperienced operators should receive instruction from someone fa...

Страница 8: ...idelines below Failure to follow the warnings and safety guidelines could result in severe injury or death 2 2 1 DO NOT run the machine indoors or in an enclosed area such as a deep trench unless adeq...

Страница 9: ...t move the machine and allow the machine to dry before servicing 2 3 5 DO NOT service the machine if your clothing or skin is wet 2 3 6 DO NOT allow untrained personnel to service this equipment Only...

Страница 10: ...003A wc_si000108gb fm 8 2 4 Label Locations wc_gr001298 PETROL G A S O L I N A I S S I N C I BENZIN CALDO H E I S S HOT C H A U D D A N G E R G E F A H R P E L I G R O D A N G E R D A N G E R G E F A...

Страница 11: ...labels are described below Label Meaning WARNING Hot surface Close the choke Gasoline Potential Earth WARNING Electric shock will cause serious injury or death WARNING Electric shock hazard Read oper...

Страница 12: ...erial number is attached to each unit Please record the information found on this plate so it will be available should the nameplate become lost or damaged When ordering parts or requesting service in...

Страница 13: ...single phase Brushless capacitor regulator system AC Voltages Available Volts phase 230 1 Frequency Hz 50 Power Factor 0 9 AC receptacles 230V 16Amp Schuko 230V 16Amp French 230V 16Amp Swiss 230V 16Am...

Страница 14: ...phase brush type compound regulator system AC Voltages Available Volts phase 230 1 400 3 Frequency Hz 50 Power Factor 0 8 AC receptacles 230V 16Amp Schuko 230V 16Amp French 230V 16Amp Swiss 230V 16Amp...

Страница 15: ...LWA GV 7000A GV 7003A Engine Engine Make Honda Engine Model GX390K1 VPX4 Rated Power kW Hp 8 3 11 1 Spark Plug BPR6ES W20EPR U Electrode Gap mm in 0 7 0 8 0 028 0 031 Engine Speed full load rpm 3000...

Страница 16: ...pliance contact the tool manufacturer for wattage requirements Some appliances and tools require a surge of current when starting This means that the amount of power needed to initially start the equi...

Страница 17: ...trical tools often require a large starting current The amount of starting current depends on the type of motor and its use Most electrical tools require 1 2 3 times their stated wattage for start ing...

Страница 18: ...the generator must be installed indoors adequate ventilation or exhaust hoses must be provided When venting exhaust fumes make sure the exhaust piping is large enough to prevent excessive back pressu...

Страница 19: ...tude also affects the cooling capacity of air the higher the altitude the less dense the air is and thus the lower its ability to transfer heat For every increase in altitude of 500 m 1650 ft above 10...

Страница 20: ...n bare or frayed cords Replace damaged cords immediately Do not exceed the rating of the cord Contact the cord manufacturer if in doubt about cord use Choose the cord size from the Minimum Extension C...

Страница 21: ...50 100 200 Cross sectional area of wire in mm2 2 1 5 1 5 1 5 1 5 1 5 1 5 1 5 1 5 4 1 5 1 5 1 5 2 5 1 5 1 5 1 5 1 5 6 1 5 1 5 1 5 4 1 5 1 5 1 5 2 5 8 1 5 1 5 2 5 6 1 5 1 5 1 5 2 5 10 1 5 1 5 4 6 1 5 1...

Страница 22: ...PE stud to earth ground Refer to local codes if machine is used to power a building or similar distribution system 4 7 Operating Heavy Loads Limit operations requiring the maximum rated output of the...

Страница 23: ...nd make sure their power requirements do not exceed the power rating of the generator or the current limit of the receptacles Note Enlargements of receptacles show protective covers removed for identi...

Страница 24: ...aker 10 A 12 A 10 A 3 Pole f1 Schuko IP54 CEE 7 receptacle 230V 16 Amp f2 CEE receptacle IP44 2P E 230 V 16 A f3 Swiss receptacle 230 V 16 A f4 French receptacle 230 V 16 A g1 CEE receptacle IP44 3P N...

Страница 25: ...and understand safety and operating instructions at beginning of this manual 4 9 2 Read and understand the meanings of all warning and operating labels 4 9 3 Check oil level in engine fuel level condi...

Страница 26: ...rope d Note If the oil level in the engine is low the engine will not start If this happens check oil level and add oil as needed 4 10 4 Open choke as engine warms b 4 10 5 Place main circuit breaker...

Страница 27: ...dic Maintenance Schedule Daily before starting After first 20 hrs Every 50 hrs Every 100 hrs Every 300 hrs Check fuel level Check engine oil level Inspect air filter Replace as needed Check external h...

Страница 28: ...the interests of environmental protection place a plastic sheet and a container under the machine to collect any liquid that drains off Dispose of this liquid in accordance with environmental protecti...

Страница 29: ...int solvents for cleaning the air cleaner A fire or explosion could result To service 5 4 1 Release latches a on the top and bottom of the air cleaner cover b and remove the cover 5 4 2 Check the filt...

Страница 30: ...ping the engine Do not touch the muffler while it is hot Note Refer to the Technical Data for the recommended spark plug type and the electrode gap setting 5 5 1 Remove the spark plug and inspect it 5...

Страница 31: ...engine to the proper speed Turn the speed adjusting screw a in or out to obtain a no load speed of 3100 rpm CAUTION Setting the engine speed too high or too low may damage tools and other appliances a...

Страница 32: ...oil into the cylinder Crank the engine a few turns to distribute the oil to the inside of the cylinder walls 5 7 6 Pull the starter rope slowly until resistance is felt and leave the handle in this po...

Страница 33: ...e should be closed when starting a cold engine All loads are disconnected from generator Spark plug is in good condition Spark plug cap is tight Engine oil level is adequate If engine starts but there...

Страница 34: ...sorber 2 Auxiliary Winding 7 Circuit Breaker 3 Capacitor 8 Receptacle 230 V 1 16 A 4 Rotor Windings 9 Receptacle 230 V 1 32 A 5 Diode Wire Colors B Black V Violet Or Orange G Green W White Pr Purple L...

Страница 35: ...Receptacle 230 V 1 16 A 4 Rotor Windings 9 Receptacle 400 V 3 16 A 5 Compound transformer 10 Brushes Wire Colors B Black V Violet Or Orange G Green W White Pr Purple L Blue Y Yellow Sh Shield P Pink...

Страница 36: ...Maintenance GV 7000A 7003A wc_tx000274gb fm 34 Notes...

Страница 37: ...ositions de la directive 2000 14 CEE and has been produced in accordance with the following standards und in bereinstimmung mit folgenden Richtlinien hergestellt worden ist y ha sido fabricado en conf...

Страница 38: ......

Страница 39: ...ositions de la directive 2000 14 CEE and has been produced in accordance with the following standards und in bereinstimmung mit folgenden Richtlinien hergestellt worden ist y ha sido fabricado en conf...

Страница 40: ...02 0 Fax 49 0 89 3 54 02 3 90 Wacker Corporation P O Box 9007 Menomonee Falls WI 53052 9007 Tel 262 255 0500 Fax 262 255 0550 Tel 800 770 0957 Wacker Asia Pacific Operations Skyline Tower Suite 2303 2...

Отзывы: