44
UR3274U - User manual
30
a.1.s.p.
Alarm 1 Setpoint Protection
does not allow the user to modify setpoint.
Free
>
Default
Lock.
Locked
Hide
Locked and hidden
31
aL. 2
Alarm 2
Alarm 2 selection. Alarm intervention is associated to AL2.
dis.
Disabled >
Default
a. aL.
Absolute Alarm
b. aL.
Band Alarm
H.d.aL.
High Deviation Alarm
L.d.aL.
Low Deviation Alarm
a.c.aL.
Absolute Command setpoint Alarm
st.aL.
Start Alarm, Attivo in Run
CooL
Cooling
t.1.s.a.
Timer 1 Start Alarm
t.1.e.a.
Timer 1 End Alarm
t.1.w.e.
Timer 1 Warning Expiring
t.2.s.a.
Timer 2 Start Alarm
t.2.e.a.
Timer 2 End Alarm
t.2.w.e.
Timer 2 Warning Expiring
t.1.2.s.
Timer 1-2 Start Alarm
t.1.2.e.
Timer 1-2 End Alarm
t.1.2.w.
Timer 1-2 Warning Expiring
32
a.2.s.o.
Alarm 2 State Output
alarm 2 output contact and intervention type.
n.o.s.
(n.o. start) Normally open, active at start. >
Default
n.c.s.
(n.c. start) Normally closed, active at start.
n.o.t.
(n.o. threshold) Normally open, active on reaching alarm
6
n.c.t.
(n.c. threshold) Normally closed, active on reaching alarm
6
6
On activation the output is inhibited if the controller is in alarm mode.
Activates only if alarm condition reappers, after that it was restored.