6 Mainboard test
IMPORTANT NOTE:
Machine disconnected from any A/C system or refrigerant tank!
Check that both
HP
and
LP
gauges show zero pressure!
1. Select
SERVICE
and type password:
228482
The display shows:
(1)
CONTROLLED OUTPUT
(2)
REFRIGERANT SCALE
Net compensated value.
(3)
USED OIL SCALE
Net compensated value.
(4)
PRESSURE TRANSMITTER
Absolute pressure compensated value.
(5)
KEY ID. number
(6)
TEMPERATURE
Mainboard “A” (PWR) [tenths of °C].
(7)
TEMPERATURE
Mainboard “B” (Display) [tenths of °C].
(8)
REFRIGERANT SCALE
Analog to digital converter points.
(9)
USED OIL SCALE
Analog to digital converter points.
(10)
PRESSURE TRANSMITTER
Analog to digital converter points.
KEY IDENTIFICATION NUMBER
The number identifies the pressed key as described below:
0
No key pressed
2
ENTER
key (The
ENTER
key activates the output indicated on the display, read the instruc-
tions before use)
4
STOP
key (Not visible)
8
START
key
16
X
(CANCEL)
key
32
RIGHT
key
64
i
(INFO)
key
128
LEFT
key
CP 0 TA209 TB208
1240 8850000
21 4000
50 2890
2
3
4
5
6
7
8
9
10
1
Содержание COOLIUS A30
Страница 2: ...2 COOLIUS A30...
Страница 4: ...4 COOLIUS A30 1 Flow diagram SN FROM AC000140 TO AC000302 AND FROM AC000305 TO AC000311 INCLUDED...
Страница 5: ...5 COOLIUS A30 SN AC000303 AC000304 AND STARTING FROM AC000312 INCLUDED...
Страница 7: ...7 COOLIUS A30 2 Electric diagram...
Страница 9: ...9 COOLIUS A30 3 Machine description...