5.4.4 F_OFFSET (Feedback offset)
Command
Parameters
Unit
Group
CDWIN
X
x= -50000… 50000
mbar
EXP
This parameter is entered in mbar.
This parameter adds an offset value to the resulting feedback signal.
For example, to compensate external
power differences (suspended loads, spring forces ect.).
5.4.5 SIGNAL (Type of input signal)
Command
Parameters
Unit
Group
SIGNAL:I X
SIGNAL:Q X
i= X1|X2|W
x= OFF|U0-10|I4-20|
U10-0|I20-4
x= OFF|U0-10|I4-12-20|
U10-0|I20-12-4
-
V|mA
EASY
This command can be used to change the type of input signal (voltages or current) and to define the direction
of the signal. This command is available for all analogue inputs (X1, X2, W and Q).
OFF= Deactivation of the input.
5.4.6 N_RANGE (Nominal pressure of the sensor)
Command
Parameters
Unit
Group
N_RANGE:I X
i= X1|X2
x= 10… 1000
bar
EASY
This parameter is entered in bar.
N_RANGE is used to define the nominal value of the sensor. This value should be always higher than
SYS_RANGE. The control parameter cannot be calculated correctly in case of wrong values.
5.4.7 OFFSET (Sensor offset)
Command
Parameters
Unit
Group
OFFSET:I X
i= X1|X2
x= -60000…60000
mbar
EASY
This parameter is entered in bar. Adjustment of zero point of the sensor is realized with it.
Xi(result) = Xi(analogue)
– „OFFSET:Xi x“