Page 21 of 34
PQ-132-U
5.3 Basic parameters
5.3.1 LG (Changing the language)
Command
Parameters
Unit
Group
LG
x
x= DE|EN
-
STD
Either German or English can be selected for the help texts.
CAUTION:
After changing the language settings, the ID button in the menu bar (WPC-300) must be
pressed (module identification).
5.3.2 MODE (Parameter view)
Command
Parameters
Unit
Group
MODE
x
x= STD|EXP
-
STD
This command changes the operating mode. Various commands (defined via STD/EXP) are blanked out in
Standard Mode. The commands in Expert Mode have a more significant influence on system behavior and
should accordingly be changed with care.
5.3.3 SENS (Malfunction monitor)
Command
Parameters
Unit
Group
SENS
x
x= ON|OFF|AUTO
-
STD
This command is used to activate/deactivate the monitoring functions (4… 20 mA sensors, output current, sig-
nal range and internal failures) of the module.
ON:
All monitoring functions are active. Detected failures can be reset by deactivating the ENABLE in-
put.
OFF:
No monitoring function is active.
AUTO:
Auto reset mode. All monitoring functions are active. If the failure doesn’t exist anymore, the mod-
ule automatically resumes to work.
Normally the monitoring functions are always active because otherwise no errors are detectable via
the READY output. Deactivating is possible mainly for troubleshooting.