WIRING DETAILS
May 2, 2011
Communications Wiring
|
JACE-700 MOUNTING AND WIRING GUIDE
Part Number 11694 Rev 1.6
19
Figure 7 JACE-700 controller communications ports.
Ethernet
Two, female 1-Gigabit Ethernet connections are provided on the controller. These
are RJ-45 connectors labeled LAN1 and LAN2. Use a standard Ethernet patch cable
for connecting to a hub or Ethernet switch.
The factory-default IP address for LAN1 is
192.168.1.12n
, where the last
numeral
n
in the address matches the last digit in the controller’s serial number, and
the subnet mask is
255.255.255.0
.
By default, LAN2 is disabled.
Refer to the
JACE NiagaraAX Install and Startup Guide
for details on changing IP
address.
Note
Typically, you
only use LAN1
(primary port), unless you have a specific
application for the other LAN2 port. For example, isolating a driver’s
network traffic, using LAN2. Do
not
use LAN2 as the primary port.
Serial
There are two “RS” serial ports on the controller’s base board. Each has a UART
capable of operation up to 115,200 baud. At the bottom of the board (see
page 19) is an
port using an DB-9 plug (male) connector. On the right side of
the unit is an isolated
port, using the bottom three terminals of a 6-position
screw-terminal connector plug.
Note
Additional serial ports may be added with option card(s) in Option Slot 1
and Slot 2, such as an NPB-485-PWR card, NPB-232 card, or NPB-2X-485
card (note the last option actually adds two serial ports).
In addition, there are two
ports—these ports are located on the top side.
Option slot 2 connector area
Option slot 1 connector area
RS-232 (DB-9) COM1
USB ports (2)
RS-485 COM2
15V PS -, + and
12V Backup Battery out
Bottom side
Right side
Top side
LAN 2 Ethernet (RJ-45)
LAN 1 Primary Ethernet (RJ-45)