Place the knob in line with its shaft.
-
Install the bulb, generally in a thermometer well (for liquids and gases) or in a cylindrical housing (for
solids) having an inside diameter slightly greater than that of the bulb so as to preserve good thermal
conduction. It is advisable to confirm the conduction using appropriate thermal grease.
66
39
38
22
29
52
48
6,35 Fastons
terminals
Support
Capillary
6
L
21
21
Ø M 3
4 - 2 - ELECTRICAL CONNECTION :
Set-up the diagram shown below :
User
1
2
4
-
Ensure that each Faston terminal is properly located and tightened.
-
Be sure to connect the ground terminal to the installation ground.
5 -
COMMISSIONING PROCEDURE :
-
Using the adjusting knob, place the index to the desired temperature setpoint value of the dial.
-
Energize the heating installation, first checking that the installation operating conditions are satisfied.
-
Before nominal temperature is reached, make sure that the thermostat knob, when turned, turns off the heating
and restarts it. Then reset the knob to the load temperature setpoint.
NOTE
: The information on the vernier of the thermostat knob is not accurate enough to be sure that the
temperature obtained is exact. Proceed by successive readjustments of the setpoint to obtain the desired
temperature, measuring it with a thermometer.
2/3