ELECTRICAL CONNECTIONS
Electrical and grounding connections must comply with the
applicable portions of the National Electrical Code and/or other local electrical
codes.
Disconnect the electrical power to the griddle and follow lockout /
tagout procedures.
Since the griddle top is not fused, you must connect to a fused circuit equipped with a
suitable disconnecting means as required by local authorities.
Electrical Connections
1. Remove the small junction box cover plate on the back of the unit. This exposes the
VMCS clamshell griddle line leads.
2. Select a suitable knockout on the sides or bottom of the junction box.
3. Connect the griddle’s line leads to the supply wires with factory supplied wire connectors as shown
in the applicable wiring diagrams.
4. Push the excess wire into the junction box and replace the cover plate. Never operate griddle
without cover in place.
ELECTRICAL SPECIFICATIONS
Model No
Description
Voltage
Power
1 Phase Draw
VMCS-101
FLAT
PLATE
208V
3.6 KW
17.3 A
VMCS-102
240V
15.0 A
VMCS-201
GROOVED
PLATE
208V
17.3 A
VMCS-202
240V
15.0 A