Cabling
Connect power leads of the control gear and
frequency converter of the fan drive according to
the Electric diagram.
The wire cross-sections have been selected for long
term current capacity for cables arranged in the air
(supported on brackets, cable racks, in perforated trays) with
spacing from the wall of min. 0.3 cable diameter, insulated with PVC,
for 3-conductors loaded.
Due to the protection selectivity, length, cable placement method
and short-circuit currents, revise the feeders’ cross-sections in the
table below.
Type
Picture
Ddescription
Parameters
[1]
Control wires with
copper cores with
a
shield.
PVC
isolation.
Nominal voltage:
300/500 V
Ambient
temperature: –30
to 80°C
[2]
Copper cores. PVC
isolation.
Nominal voltage:
450/750V
Ambient
temperature:
from –40 to 70°C
[3]
Copper cores. PVC
isolation.
Nominal voltage:
150 V
Ambient
temperature:
–
20…60°C
[4]
Flat
communication
cable
without
shield.
Nominal voltage:
150V
Ambient
temperature:
–
20…60°C
Name of element
Symbol
Type
Name of element
Analog Inputs
B1-B6
[1]
2x0,5
Analog Outputs
Y1,Y3,
Ain10V,
Aout0-
10V
[1]
3x0,5
Digital Inputs
DI1-DI6,
IN1,IN2
[2]
2x0,5
Relay Outputs
NO2-NO6
[2]
2x0,5
HMI Basic UPC –
reduced function
interface
RS-485
[3]
UTP 1x2
HMI Advanced UPC
–
full
function
interface
N3
[4]
8x0,1
HW
circulating
pump contactor
K1
[2]
3x1,5
Содержание 3x400V 1x1VFD 11kW
Страница 7: ...EN VTS reserves the right to implement changes without prior notice 7 Connection controller diagram...
Страница 15: ...EN VTS reserves the right to implement changes without prior notice 15...
Страница 17: ...EN VTS reserves the right to implement changes without prior notice 17...
Страница 19: ...EN VTS reserves the right to implement changes without prior notice 19...
Страница 21: ...EN VTS reserves the right to implement changes without prior notice 21...
Страница 23: ...EN VTS reserves the right to implement changes without prior notice 23...
Страница 26: ...EN VTS reserves the right to implement changes without prior notice 26...