VSI Series 1000-X Electric Actuator

Operation and Maintenance Manual

8

The opening and closing operation of the actuator 

is regulated with the travel limit switches which 

interrupt the power circuit to the motor.  The two 

power legs and a common are needed in order to drive 

the actuator open or closed.  Two SPDT switches are 

provided to give end of travel status indication. For 

all units, except the 1005-X, a manual override push 

button is included to isolate motor for manual hand 

crank or wheel operation. 

Y&G

GREY

BROWN

WHITE

BLACK

RED

BLUE

HEATER

OLS

CLS

C

M

PE

FULL CLOSE SIGNAL

FULL OPEN SIGNAL

COM

OPEN

CLOSE

K

L

N

PUSH BUTTON

THERMAL PROTECTOR

ACTUATOR

FIELD WIRING

GND

7
6

5

4

3

2

1

Power must be removed from actuator using manual 

override pushbutton, or disconnect/circuit breaker for the 

1005-X, before manual operation.  If manual operation is 

attempted with power connected actuator handwheel or 

crank may rotate and cause personnel injury.

WARNING

Models

Contact Ratings

AC Voltage

DC Voltage

1005-X and 1005-XL

3A/250VAC

NR

1010-X thru 1250-X

15A/250VAC

0.6A/125VDC

1. Power Common
2. Close Operation (Power Hot)
3. Open Operation (Power Hot)
4. Auxiliary Contact Common
5. Auxiliary Contact Open Status
6. Auxiliary Contact Close Status
7. Chassis Ground

TERMINAL WIRING

ELECTRICAL WIRING CONNECTION

POWER SUPPLY REQUIREMENTS

• Power supply for the corresponding unit must 

meet the electrical requirements for voltage and 

current ratings as show in its specifications.

•  The power supply tolerance shall be as follows:

Rating

24 V

110V

220V

Range

21.6V-26.4V 99V-121V

198V-242V

Frequency

60 Hz

Rating

24V

110V 220V

1005-X & 1005-XL

5A

3A

2A

1010-X

7A

5A

3A

1020-X & 1040-X

10A

7A

5A

1060-X

NA

7A

5A

1100-X, 1160-X, & 1250-X

10A

7A

Circuit Breaker Fuses

Recommended fuses for circuit breakers are as  

follows:

Model

Transformer

1005-X & 1005-XL

50VA

1010-X

50VA

1020-X

150VA

1040-X

200VA

24VAC Transformers

Minimum recommended 120V/24V power transformer 

ratings are as  follows:

Care should be taken sizing and wiring 120V/24V 

transformers, considering wiring transformer primaries in 

series will split voltage and in parallel will split current.

~V

2IN

~V

1IN

~V

IN

 TOTAL

   =V

1IN

+V

2IN

~V

2OUT

~V

1OUT

Содержание 1000-X Series

Страница 1: ...ANCE MANUAL VER0815 2 For information on this product and other VSI products please visit our web page www valvesolutions com COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION OPEN CLOSE SERVICE ELECTRI...

Страница 2: ...wiring should follow these diagrams Do not manually operate the actuator without deenergizing actuator with factory installed push button or by external disconnect such as a circuit breaker NOTICE Va...

Страница 3: ...ar Group 4 Front Wiring Cover 14 Capacitor 5 Push Button 15 Open Cam Lock Screw 6 Conduit Plugs 16 Close Cam Lock Screw 7 Hex Handle 17 Position Indicator 8 Hex Handle Bracket 18 SPDT Limit Switches 9...

Страница 4: ...220 VAC Motor Power 10W Rated Current 1 7A 0 24A 0 16A Max Current 1 9A 0 34A 0 17A Standard Torque 443inlb 50NM Run Time 1005 X 17 0 5 sec 1005 XL 21 0 5 sec Turning Angle 90 Adjustable 5 Total Weigh...

Страница 5: ...Max Current 2 40A 0 81A 0 52A Standard Torque 885inlb 100NM Run Time 24 5 0 5 sec Turning Angle 90 Adjustable 5 Total Weight 9 10lbs 4 13kg Insulating Resistance 100M 250VDC 100M 500VDC Overvoltage Wi...

Страница 6: ...8A 3 41A 3 60A Total Weight 19 4lbs 8 80kg 20 9lbs 9 46kg 20 9lbs 9 463kg 220VAC Motor Power 40W 90W 90W Rated Current 0 37A 0 57A 0 60A Max Current 0 78A 1 78A 1 87A Total Weight 19 7lbs 8 91kg 21 2l...

Страница 7: ...tor Power 140W 140W 140W Rated Current 0 94A 0 98A 0 98A Max Current 2 12A 2 20A 2 20A Total Weight 41 2lbs 18 7kg 41 9lbs 19 0kg 42 4lbs 19 2kg Standard Torque 8 850inlb 1 000NM 14 160inlb 1 600NM 22...

Страница 8: ...ltage DC Voltage 1005 X and 1005 XL 3A 250VAC NR 1010 X thru 1250 X 15A 250VAC 0 6A 125VDC 1 Power Common 2 Close Operation Power Hot 3 Open Operation Power Hot 4 Auxiliary Contact Common 5 Auxiliary...

Страница 9: ...ating coupling in lieu of direct mounting to valve WARNING Medium Radiant Heat Refer to Figure 1 1 and 1 2 when connecting conduit to Series 1000 X actuators Conduit entries are NPT All entry fittings...

Страница 10: ...Attach the bracket with proper bolts and tighten all bolts If bolt holes are not aligned but within Installation of Actuator to Valve 5 alignment rotate actuator handwheel to move actuator into alignm...

Страница 11: ...e plate Dome indication Full open position Full close position Lock screw Opening gear Shut position regulating shaft Openpositionregulatingshaft S Red O Green D2 D1 O S K1 K2 K3 K4 Open direction mid...

Страница 12: ...ltage The actuator is in thermal protection mode due to over torque situation or ambient temperature is too high Remove over torque conditions Check valve to ensure manual movement without sticking Co...

Отзывы: