VSL3.780.052ASY

V1.03

Heat Sensor setting

Mode

Class

Application Temperature

Static Response Temperature

Typical

Maximum

Min

Max

1

A1R

25

50

54

65

2

A2

25

50

54

70

Mode 1

is Factory Setting.

The letter “R” suffix means that the heat response class incorporates a rate-of-rise characteristic. It will give
rapid response even when high rates of rise of air temperature starting at air temperatures substantially
below the typical application temperature.

The VI-6647 heat response mode can be set by Control Panel, please refer to the corresponding manual for
details.

Testing

Warning

Power is switched off before all devices are installed completely.

The detector must be tested after installation or regular maintenance.

Registration:

The fire alarm control panel will registers the detector on line to check if the address of the

detectors mounted is the same address as that registered in the control panel.

Fire condition:

After registration, make detector under fire conditions by using hot air generator and/or

Smoke generator to test whether the detector alarms normally and control panel displays its registered
address.

Reset

After testing, reset the detector through control panel.

Fault Finding

Detector Fault on
Control Panel

Check wiring of Common base, no water no short-circuits and open circuit.
Check the connection between detector and common base.

Nuisance alarm

The detector alarm frequently but there is no Fire and other unusual, then check whether

the chamber in the detector is too dirty and needs to be cleaned

Otherwise, the circuit may be broken.

Address Fault

Address is set incorrectly, Reset by VI-6537 Digital Programmer.

Cautions

Dust cover on the detector shouldn’t be removed between installation and acceptance test to avoid
contamination.

If the detector gives fault warning after a long operation, first check if the chamber in detector are too dirty, or
the position is changed. At last, other faults should be considered.

Fire alarm test requirement as specified in the applicable local codes, we suggest to test every 6 month.

Please put on the dust cover if the room is decorated or wall-painted to avoid contamination.

Limited Warranty

VSAIL warrants that the product will be free of charge for repairing or replacing from defects in design, materials
and workmanship during the warranty period. This warranty doesn’t cover any product that is found to have been
improperly installed or used in any way not in accordance with the instructions supplied with the product. Anybody,
including the agents, distributors or employees, is not in the position to amend the contents of this warranty.
Please contact your local distributor for products not covered by this warranty.