background image

OSPZX225-EN 

9/10 

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

OPERATION 

AIR SOURCE 

• Use the filtered dry air (less than 40  ).   
• Extra attention is needed where it's cold climate 

(below 5 °C).   

• When air pressure is high, reduce it to standard 

pressure (0.4 to 0.7 MPa). Air pressure should not 
exceed 0.7 MPa during operation test.   

• Capacity of compressor and air tank are to be 

calculated by capacity of piping and air consumption.   
A margin of 30% is required.   

TEST OPERATION 

Check the operation of pneumatic actuator before 
fluid enters the piping.

Double-acting type  Stop the air from the air source. 

Release the residual pressure 
in the air cylinder. Open the air 
equalizer. Move the manual 
shaft of actuator with a wrench. 

Single-acting type  Send the standard pressure air. 

Confirm the opening / closing 
operation by slowly moving the 
actuator.   

TESTING 

After piping, check following points. 

• Piping is correct.   
• Air or fluid leakage from connection. Flow 

direction of air is correct.   

• Air pressure is in the range.   
• Nothing interferes with operation when limit 

switch or solenoid valve is attached.   

ATTENTION 

The opening and closing operation of the pneumatic 
actuator is fast, which may affect the product life.   
Please adjust the operation time of pneumatic 
actuator using a speed controller.   

Valve size [mm] 

Adjustment of operation time. 

Less than 040 

More than 1 second 

050 or more 

More than 2 seconds 

MANUAL OPERATION 

• Double-acting; stop the air supply and do not leave 

the air inside of cylinder.   

• Single-acting; cannot be operated manually.   

Optional code with the handle: TAO-MT / TAC-MT. 

• Before automatic operation, be sure to remove 

wrench.   

OPERATION (PND / TAD) 

After turning air pressure to 0, turn manual shaft 
slowly with a smooth-jawed wrench to check the 
direction of OPEN/SHUT position. 

PND 

TAD 

MAINTENANCE 

• Do the routine maintenance at least once in half a 

year.   

• Do not set or take spring unit parts apart after 

installing the pneumatic single-acting actuator.   

Can be used with no oil supply. 

• Confirm the air leakage.   
• Confirm the air supply pressure.   
• Confirm the dirt or grit inside of cylinder.   

Lubrication Procedure (TAD / TAO / TAC)   
In case of lubricating, use turbine oil or the 
equivalent through a lubricator. (ISO VG 32.46). 
Once lubricate, do the regularly. 

Inspection items 

• Confirm operation of opening and closing.   
• Confirm whether screws are loose or not.   
• Confirm the fluid temperature or pressure. 
• Confirm the leak from valve stem.   
• Confirm the bolt tightening torque.   

Manual shaft

Содержание PND-03D

Страница 1: ...10 11 1 Actuator PND TAD PSO TAO PSC TAC 2 Valve Z 3 Voltage 9 Air 4 Sizing code 0 Standard 1 Light 2 Heavy 5 Connection 5 Threaded End Rc 7 Socket End 6 Body material T SCS13A 7 Cap Socket U SCS14A...

Страница 2: ...A Disc PPS Cap SCS14A Socket PVC C PVC Seat EPDM NBR FKM Stem seal O ring Depend on seat material SEAT MATERIAL GUIDE Seat material Fluid temp Use EPDM 20 to 80 C NBR 10 to 60 C FKM 0 to 90 C Note EPD...

Страница 3: ...ates the upper shaft of the actuator directly PSO PSC type Classification Single acting type Spring return Actuator type PSO 03S PSC 03S PSO 03D PSC 03D PSO 04D PSC 04D PSO 05D PSC 05D PSO 05W PSC 05W...

Страница 4: ...perates the upper shaft of the actuator directly TAO TAC type Classification Single acting type Spring return Actuator type TAO 040 TAC 040 TAO 050 TAC 050 TAO 063 TAC 063 TAO 080 TAC 080 TAO 100 TAC...

Страница 5: ...Smart positioner ES ER Smart positioner with 4 to 20mA output ET EU SHUTby 4 mA OPENby 20 mA A SHUTby 20 mA OPENby 4 mA B OPENby 20 mA SHUT by 4 mA Airless SHUT C OPENby 4 mA SHUT by 20 mA Airless SHU...

Страница 6: ...r with lamp 4N3S102K N N43SN Watertight cover 4N3S102K W N43SW 5 port Explosion proof solenoid valve Return with bypass valve Conduit 4N4S102K E01 H B0 R 4N4S01 B0 NO Flame proof packing Cable size 9...

Страница 7: ...tor H W N N1 TAD 040 89 5 110 57 32 TAD 050 123 170 82 36 TAD 063 138 204 95 38 TAD 080 171 240 116 45 TAD 100 202 294 143 57 TAD 125 227 366 150 60 TAD 160 273 446 181 68 TAO TAC Note Cylinder direct...

Страница 8: ...Refer to the recommended tightening torque table and do not apply excessive torque Valve size mm Torque N m 015 25 to 35 020 40 to 50 025 50 to 60 032 60 to 80 040 75 to 85 050 90 to 110 Socket End S...

Страница 9: ...he pneumatic actuator is fast which may affect the product life Please adjust the operation time of pneumatic actuator using a speed controller Valve size mm Adjustment of operation time Less than 040...

Страница 10: ...INSTRUCTIONS TROUBLESHOOTING Problem Cause Solution Fail to operate Air doesn t come out Supply air Air pressure is too low Adjust to standard pressure level Stop in the mid position Biting of valve s...