Page 2 of 4
Vox Power Limited | Unit 2, Red Cow Interchange Estate, Ballymount, Dublin 22, D22 Y8H2, Ireland | T +353 1 4591161 |
DOC-MN-002-05, NEVO+1200 Series Installation Manual
Specifications
INPUT MODULE SPECIFICATION SUMMARY
Parameter
Details
Min
Typical
Max
Units
AC Input Voltage
Nominal range is 100V
RMS
to 240V
RMS
85
264
V
RMS
AC Input Frequency
Contact factory for 400Hz operation.
47
50/60
63
Hz
DC Input Voltage
Not covered by safety approvals. Contact Vox Power.
120
370
V
DC
Output Power Rating
Standard & Medical (S/M) - De-rate linearly from 1200Watts at 120V
RMS
to 850Watts at 85V
RMS
Low Noise (SL/ML) - De-rate linearly from 900Watts at 120V
RMS
to 638Watts at 85V
RMS
1200
900
Watts
Input Current
Standard & Medical (S/M) - 1200Watts output at 120Vrms input
Low Noise (SL/ML) - - 900Watts output at 120Vrms input
12
9
Amps
Fusing
Live line fused (5x20 Fast acting)
12
Amps
Power Factor
0.99
Size
154.5 (L) x 152.4 (W) x 41.0 (H) (see diagram for tolerance details)
mm
Weight
720 + 60 per output module
Grams
Note 1.
Note 2.
NEVO+ input modules can only be used with NEVO+ output modules and must not be used for any other purpose.
Only use a power source of the type indicated on the product label.
OUTPUT MODULE SPECIFICATION SUMMARY
MODEL
Output Voltage
Output
Current
Rated
Power
Peak
Power
Load
Reg.
Line
Reg.
Cross
Reg.
Ripple &
Noise
FPMH
(1)
Feature
Set
(2)
Min.
Nom.
Max.
OP1
1.5V
5V
7.5V
25A
125W
187.5W
±50mV
±5mV
±10mV
50mV
PP
0.5
ABCDEFG
OP2
4.5V
12V
15V
15A
150W
225W
±100mV
±12mV
±24mV
120mV
PP
0.5
ABCDEFG
OP3
9V
24V
30V
7.5A
150W
225W
±150mV
±24mV
±48mV
240mV
PP
0.5
ABCDEFG
OP4
18V
48V
58V
3.75A
150W
217.5W
±300mV
±48mV
±96mV
480mV
PP
0.5
ABCDEFG
OP5
3.3V
12V
15V
5A
2x 75W
2x 75W
±50mV
±12mV
±24mV
240mV
PP
0.75
AFG
OP8
23.2V
24V
24.7V
3.125A
2x 75W
2x 75W
±100mV
±24mV
±48mV
480mV
PP
0.75
AFG
OPA2
4.5V
12V
15V
25A
300W
375W
±100mV
±12mV
±24mV
120mV
PP
0.5
ABCDEFGH
OPA3
9V
24V
30V
15A
300W
450W
±150mV
±24mV
±48mV
240mV
PP
0.5
ABCDEFGH
Note 1.
Output module, 30˚C base, 100% load, SR332 issue 2 Method I, Case 3, Ground, Fixed, Controlled
Note 2.
A = Remote Sense, B = External Voltage control, C = External constant current control, D = Current output signal, E = Current share, F =Over Voltage protection,
G = Over temperature protection, H = Dual Slot module
SAFETY SPECIFICATIONS
Parameter
Details
Max
Units
Isolation Voltages
Input to Output (2 MOPP). Do not perform test on assembled unit
(1)
4000
V
AC
Input to Chassis (1 MOPP)
1500
V
AC
Global signals (J2) to Output/Chassis
250
V
DC
Output to Output/Chassis (Standard modules)
250
V
DC
Earth Leakage Current
INDUSTRIAL: Normal condition, 264Vac, 63Hz, 25°C
1500
uA
MEDICAL: Normal condition, 264Vac, 63Hz, 25°C
300
uA
Touch Leakage Current
Standard modules NC/SFC
20/200
uA
Patient Leakage Current
Standard modules 264Vac, 63Hz, 25°C NC/SFC
(2)
-----
uA
Note 1. Testing an assembled unit to 4000V
AC
may cause damage. Please refer to application note (APN-002) on Vox Power website or contact Vox Power representative.
Note 2. Not Applicable
INSTALLATION SPECIFICATIONS
Parameter
Details
Parameter
Details
Equipment class
I
Flammability Rating
94V-2
Overvoltage category
II
Ingress protection rating
IP10
Material Group
IIIb (indoor use only)
ROHS compliance
2011/65/EU
Pollution degree
2
Intended usage environment
Home Healthcare (M/ML)/ Industrial (S/SL)
ENVIRONMENTAL SPECIFICATIONS
Parameter
Details
Non-Operational
Operational
Units
Min
Max
Min
Max
Air Temperature
Operational limits subject to appropriate de-ratings
-40
+85
-20
70
(1)
°C
Humidity
Relative, non-condensing
5
95
5
95
%
Altitude
-200
5000
-200
5000
(2)
m
Air Pressure
52
104
52
(2)
104
kPa
Noise Level
Standard Versions (S/M) - Variable. Measured 1m from fan intake.
Low Noise Versions (SL/ML) - Variable. Measured 1m from fan intake.
42
24
61
42
dBA
Shock
3000 bumps at 10G (16mS) half sine wave
Vibration
1.5G, 10 – 200Hz sine wave, 20G for 15min in 3 axes.
Notes
1.
Derate input and all outputs at 2.5%/°C above 50°C.
2.
3000m & 68kPa for IEC/UL60601-1.