Connection and assembly
The FB filter must be installed on a ventilation line,
upstream
from
the
fan/heat
recovery
sistem,
upstream from the noise attenuator NA, and if
present, upstream from the air heater AH. To install
the air filter, it is sufficient to insert it into the tube (Fig.
1).
The appliance is connected to the system by means
of a forced insertion on two cylindrical fittings in
galvanised steel with circular rubber built-in "T" seals.
Leave sufficient space to allow the filter to be cleaned
or replaced.
Technical data
Filtering class
:
F7
Filtering media
:
F7 Filter: composit polypropylene
Max operating temperature
:
F7: 70° C
Dimensions
: fig 2.
Curves of the initial load loss of filters
:
Diagrams pag. 18.
Maintenance/cleaning
Check the filter from time to time and, if necessary,
replace it. Non reconditionable filters, which have to
be replaced when the loss of pressure is 1.5 times
above the loss that occurs when the filter is cleaned.
Clean the filter with mechanical means, a vacuum
cleaner or compressed air.
7
ENGLISH
FB
VORTNRG
NA
AH
1
1
A
B
C
E
D
2
2
Mod.
A
B
C
D
E
Kg
FB 500
235
285
300
200
400
6,5
FB 800
405
315
300
250
400
9
FB 1200
470
370
600
315
700
16
FB 2000
560
485
600
315
700
20
FB 2500
630
515
700
355
800
25
FB 4000
710
608,5
900
450
1000
34
FB 6000
710
805
900
450
1000
40
Содержание FB 1200