Operating the VN2000 Transmitter
Page 20
June 2017
VRX-UM-02233-EN-02
Tpplication
The
Application
option sets up the flow meter for the desired fluid type and application . The
Application
is factory-set . The
setting is based on the application fluid type and should NOT be changed . If the incorrect fluid type is selected, please contact
the factory immediately .
Modbus Tddress
Enter the Modbus RTU address . See the “VN2000 Flow Meters Modbus User Manual .”
Settings
Initially, the meter shows field settings that have been factory-set for your particular application parameters .
This option lets you reset all program settings to factory settings, if required . DO NOT change to factory settings unless
advised to do so by the manufacturer .
Vibration Control
The
Vibration Control
settings block out unwanted vibration or other frequencies that may affect the flow meter accuracy
or repeatability .
High
The highest vibration control setting helps with no-flow condition and active flow condition . Use in locations
where vibration is present
Medium
Good vibration control helps with no-flow condition and active flow . Use this setting for steam and gases
Low
Basic vibration control during no-flow condition and active flow . Use this setting for liquids
Off
No vibration control activated
\
Table 9: Vibration control settings