UNIFREM v.3.41x
10 May 2017
Page 82 from 180
Relay 3
Group of parameters number [188]
Relay 3 setting. Not available for the UNIFREM 400 M converter. Relay is connected to the terminals: NC -
X2:31, COM - X2:32, NO - X2:33.
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ RELAY OUTPUTS \ RELAY 3
Name [ID]
Description
Def.
R3
Source
[699]
Relay switching function setting. Functionality is the same as RELAY 1 R1 Source
[697] (page 80).
Ready
Look choises of parameter's R1 Source [697] (page 80)
R3 switch-on
time [324]
Relay switch-on time delay.
0,00 s
0,00
s
÷
3600,00 s
After establishment of the switch condition, the relay will switch-on after a selected amount
of time.
R3 switch-off
time [325]
Relay switch-off time delay.
0,00 s
0,00
s
÷
3600,00 s
If the switch condition is no longer valid, the relay remains switched on for a selected
amount of time.
R3 Logic [757]
Determines the relay output evaluation mode. The condition will be evaluated first,
then the switch times will be evaluated and the relay logic will be evaluated last.
Direct
Direct
If the switch conditions are met, the relay will switch on.
Inverted
If the switch conditions are met, the relay will switch off.
SPECIAL SETTING R3
Group of parameters number [226]
Special function setting for relay 3. R3 Source [699] (page 82) must be chosen as "Special". Not available
for the UNIFREM 400 M converter.
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ RELAY OUTPUTS \ RELAY 3 \ SPECIAL SETTING R3
Name [ID]
Description
Def.
R3 Signal [320]
Signal that is evaluated for the relay switch. Either numeric or discrete
signal can be chosen.
[76]
Converter
state
Signal
R3
switch-on
[321]
Conditions for R3 switch-on.
Ready
Look choises of parameter's Converter state [76] (page 23)
R3
switch-off
[322]
Conditions for R3 switch-off.
Look choises of parameter's Converter state [76] (page 23)
7.6.4 ANALOG OUTPUTS
Group of parameters number [145]
Analog outputs settings. Analog outputs are used to transfer continuous signals and quantities of the
converter to superior control and diagnostic systems such as display units, PLC or measuring instruments.
AO1
Group of parameters number [370]
First analog output is connected to the terminal: Plus - X1:19, Minus - X1:20 (Plus -
X1:15, Mínus
- X1:16 for
UNIFREM 400 M).
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ ANALOG OUTPUTS \ AO1
Name [ID]
Description
Def.
AO1 Type [358]
Analog output type.
0-20mA
Turned off
Analog output is turned off. The output is 0mA.
0-20mA
Analog output operates in the 0-20mA range.
4-20mA
Analog output operates in the 4-20mA range.
AO1 Source [1076]
Analog output quantity selection.
Freq. INV abs.