UNIFREM v.3.41x
10 May 2017
Page 113 from 180
Name [ID]
Description
Def.
[1155]
the order of the selections. Communication address is then calculated as a sum of the
external address and the parameter Converter address [234] (page 112).
Look choises of parameter's Bit1 DS mask [553] (page 55)
Statistics
reset [238]
Statistics reset in the serial communication diagnostics. (number of messages, number
of fault messages,...)
7.10.1 MODBUS
Group of parameters number [658]
Setting the MODBUS communication protocol. VONSCH implementation of MODBUS protocol is MODBUS
RTU specification compliant.
Detailed description of MODBUS communication protocol can be found on www.vonsch.sk, in the section
Support.
MENU \ SETTINGS \ COMMUNICATION \ MODBUS
Name [ID]
Description
Def.
Baud RS485
[218]
RS 485 serial port communication baud rate setting.
115,200
Bps
9600 Bps
19,200 Bps
38,400 Bps
57,600 Bps
115,200 Bps
128,000 Bps
115,200s Bps
Baud rate with corrected timing between frames, suitable for SIMATIC S7-1200.
Baud
ext.
module [230]
Extension module serial port communication speed. Extension module is optional.
115,200
Bps
Look choises of parameter's Baud RS485 [218] (page 113)
MB Idle [961]
Selecting how the converter should react when it is not communicating with the
Modbus master.
After the defined idle time the warning occurs, or the fault. Or first the warning and
then the fault.
□ Fault
The converter generates the fault " E42-Modbus Timeout (page 33)", when no valid request
or broadcast (if allowed) is received from the Modbus master within the preset time.
□ Warning
The converter generates the warning " W42-Modbus Timeout (page 30)", when no valid
request or broadcast (if allowed) is received from the Modbus master within the preset time.
□ Fault CW
The converter generates the fault " E42-Modbus Timeout (page 33)", when no control word
or setpoint is received in valid request or broadcast(if allowed) from the Modbus master
within the preset time.
□ W
arning CW
The converter generates the warning " W42-Modbus Timeout (page 30)", when no control
word or setpoint is received in valid request or broadcast(if allowed) from the Modbus master
within the preset time.
MB
Fault
timeout [659]
Timeout of communication interruption with Master. After this time, fault E42-
Modbus Timeout (page 33) is generated.
5,00 s
0,10
s
÷
3600,00 s
MB Warning
timeout [962]
Timeout of communication interruption with Master. After this time, warning "
W42-Modbus Timeout (page 30)" is generated. If a Modbus protocol fault and
warning are evaluated at the same time, see MB Idle [961] (page 113), then this
parameter must be lower than the parameter MB Fault timeout [659] (page 113),
otherwise the warning will not be generated.
2,00 s
0,10
s
÷
3600,00 s
MB Warning
mode [963]
Defines what action should the converter take after Modbus warning occurs.
Reset
Look choises of parameter's PB Warning mode [816] (page 116)
Broadcast
[1156]
Turning on / off the broadcasts. Broadcast is a message which is sent to all
recipients simultaneously.
Yes