Name [ID]
Description
Def.
Filter
dIRC1,2
[1083]
Time constant of the IRC1 and IRC2 frequency difference filter.
100 ms
0 ms ÷ 10000 ms
It helps to eliminate short differences caused by short dynamic shocks and unequal
loads. Filter is inactive if the value is set to 0s.
Minimal
IRC1,2
difference [1084]
Minimal limit of the absolute value for the IRC1 and IRC2 frequency difference. 2,00 Hz
0,00 ÷
Maximum IRC1,2
difference [1085]
Maximal limit of the absolute value for the IRC1 and IRC2 frequency difference. 5,00 Hz
0,00 Hz ÷ 500,00
Hz
7.7.9 DIFFERENTIAL
Group of parameters number [1239]
Parameters for the differential e.g. for the needs of torque equalization for center differential.
MENU \ SETTINGS \ FUNCTIONS \ DIFFERENTIAL
Name [ID]
Description
Def.
Sig.1 Source [1248]
Signal 1 value source.
[69] Torque
Signal
Sig.1 Value [1249]
Value 1 for PI controller of differential.
0,00
-
1E09 ÷ 1E09
Sig.2 Source [1247]
Signal 2 value source.
-
Signal
Sig.2 Value [1240]
Value 2 for PI controller of differential.
0,00
-
1E09 ÷ 1E09
Max. freq. diff. [1241]
The maximum value of the action to setpoint frequency.
0,00 Hz
0,00 Hz ÷ 20,00 Hz
P gain of diff. [1242]
Proportional gain of controller of the differential.
0,0000
-
100,0000 ÷ 100,0000
I gain of diff. [1246]
Integral gain of controller of the differential.
0,0000
-
100,0000 ÷ 100,0000
7.8 FAULTS AND WARNINGS
Group of parameters number [136]
Setting the parameters affecting the conditions of generation and termination of converter fault states.
MENU \ SETTINGS \ FAULTS AND WARNINGS
Name [ID]
Description
Def.
Clear
history
[500]
This command clears the converter fault history. There will be no record in the
history.
7.8.1 OPTIONAL FAULTS
Group of parameters number [190]
Turning on / off the evaluation of some fault states.
MENU \ SETTINGS \ FAULTS AND WARNINGS \ OPTIONAL FAULTS
Name [ID]
Description
Def.
Input phase loss
[337]
Turning on the converter input phase loss evaluation.
It is recommended to leave the input phase loss evaluation turned on, because
in the converter continuous two-phase operation there is a risk of damage to
the power capacitors. It is turned off in special cases only, when the supply
grid is of poor quality or when the fault " E13-Input phase loss (page 32)"
Is
evaluated