VON MODEL SST15-832 ARC REFLECTION SECTIONALIZING SYSTEM Page 6
V CONTROLS AND INDICATORS
ON- OFF
switch operates the main power.
START
pushbutton - When the "START" pushbutton is pushed the motorized discharge
switch opens, the motorized gap opens, and the high voltage supply begins charging the
internal capacitor bank to the set limit. The “START” pusbutton also toggles the TDR
between arc reflection and radar modes. In the RADAR position the sentence "WAITING
FOR THUMPER" must appear at the top, If “WAITING FOR THUMPER” does not show
push the “START” pushbutton a second time. “WAITING FOR THUMPER” indicates the
system is armed and can be triggered by a "thump" The trigger pulse from the thump starts
the ARC REFLECTION SEQUENCE. After a very short delay which is controlled by the
DELAY switch, a radar pulse is injected into the faulted cable. The resulting waveform is
automatically transferred into the bottom trace.
STOP
pushbutton- Drops out the high voltage ready relay which kills the high voltage
supply, closes the motorized discharge device to discharge any internally stored charge,
and after a delay closes the impulse control gap to discharge the output cable.
RADAR/THUMP
pushbutton- Alternates mode of operation between “Radar” or Arc
Reflection for pre-location and “Thump” for pinpointing. When in “Thump” mode, the TDR
screen will go blank, to indicate this..
VOLTAGE ADJUSTMENT
knob - adjusts the discharge voltage from a low value to the
maximum voltage of 15kV.
GAIN
button - Provides manual vertical gain adjustment from 0 to 20 dB by using the up
and down arrow keys
OPTIONS
pushbutton - Pressing the OPTION key presents a menu of available options
such as delay and left starts. This button is not normally used during operation.
RANGE
pushbutton- allows the operator to use the arrow buttons to change the range. The
width of the transmitted pulse is adjusted automatically when the range is changed. When
the power is turned on, the unit will automatically attempt to find the end of the cable and
select the appropriate range. If the software is unable to identify the end of the cable, the
default (normally 1500 foot/500m) range is automatically selected. The current range is
displayed in the bottom right hand corner of the screen.
ARROW
/
pushbuttons- Changes the function where the “brick” or onscreen is
located.
RIGHT MARKER
pushbutton - Allows the operator to use the arrow buttons to move the
right vertical line. The vertical line on the right of the display that sets the end point for all
measurements.
LEFT MARKER
pushbutton - Allows the operator to use the arrow buttons to move the left
vertical line. The vertical line on the left of the display sets the beginning point for all
measurements. When the radar is turned on the left marker is put at the saved end of the
Содержание SST15-832