7. Trouble shooting 

Situation 

Solution 

Fault 
Code  Fault Event Description 

60 

Current feedback into the 
inverter is detected. 

1.

 

Restart the inverter. 

2.

 

Check if L/N cables are not connected reversely in all inverters. 

3.

 

For parallel system in single phase, make sure the sharing current 

cables are connected in all inverters. 

For supporting three-phase system, make sure the sharing current 
cables connected the inverters in the same phase, and disconnected 

the inverters in different phases. 

4.

 

If the problem remains, please contact your installer. 

71 

The firmware version of 
each inverter is not the 
same. 

1.

 

Update the firmware of all inverter to the same version. 

2.

 

Check the version of each inverter via LCD setting and make sure 
the CPU versions are the same. If not, please contact your instraller 

to update the firmware. 

3.

 

If the problem still remains after the firmwzre is updated, please 

contact your installer. 

72 

The output current of each 
inverter is different. 

1.

 

Check if shared cables are well connected and restart the inverter. 

2.

 

If the problem remains, please contact your installer. 

80 

CAN data loss 

1.

 

Check if communication cables are connected well and restart the 

inverter. 

2.

 

If the problem remains, please contact your installer. 

81 

Host data loss 

82 

Synchronization data loss 

83 

The battery voltage of each 
inverter is not the same. 

1.

 

Make sure all inverters share the same groups of batteries. 

2.

 

Remove all loads and disconnect AC input and PV input. Then, check 
battery voltage of all inverters. If the values from all inverters are 
different, please check if all battery cables are in the same length 

and same type of material. Otherwise, please contact your installer 
for an SOP to calibrate the battery voltage of each inverter. 

3.

 

If the problem still remains, please contact your installer. 

84 

AC input voltage and 

frequency are detected 
different. 

1.

 

Check the utility wiring conncetion and restart the inverter. 

2.

 

Make sure utility starts at same time. If there are breakers installed 

between utility and inverters, please be sure all breakers can be 
turned on AC input at same time. 

3.

 

If the problem remains, please contact your installer. 

85 

AC output current 

unbalance 

1.

 

Restart the inverter. 

2.

 

Remove some excessive loads and re-check load information from 

LCD of inverters.   

3.

 

If the problem remains, please contact your installer. 

86 

AC output mode setting is 

different. 

1.

 

Switch off the inverter and check LCD setting #01. 

2.

 

For parallel system in single phase, make sure no 3P1, 3P2 or 3P3 is 
set on #01. 

For supporting three-phase system, make sure no “PAL” is set on 
#01. 

3.

 

If the problem remains, please contact your installer. 

 
 

Содержание EPS 5KW

Страница 1: ...EPS 5KW INVERTER CHARGER Version 1 0 User Manual...

Страница 2: ...tion 4 Rack Mounting 4 Battery Connection 5 AC Input Output Connection 6 Communication Connection 7 OPERATION 8 Power ON OFF 8 Operation and Display Panel 8 LCD Display Icons 9 LCD Setting 11 Display...

Страница 3: ...ot reduce this risk 5 CAUTION Only qualified personnel can install this device with battery 6 NEVER charge a frozen battery 7 For optimum operation of this inverter charger please follow required spec...

Страница 4: ...ble with mains voltage or generator power Auto restart while AC is recovering Overload Over temperature short circuit protection Smart battery charger designed for optimized battery performance Cold s...

Страница 5: ...iew 1 Operation panel 2 RS 232 communication port 3 AC input terminal 4 AC output terminal 5 Battery input 6 Circuit breaker 7 Parallel communication ports 8 Share current ports 9 Dry contact 10 Commu...

Страница 6: ...cting where to install Do not mount the inverter on flammable construction materials Mount on a solid surface Install this inverter at eye level in order to allow the LCD display to be read at all tim...

Страница 7: ...low Recommended battery cable and terminal size Model Typical Amperage Battery capacity Wire Size Ring Terminal Torque value Cable mm2 Dimensions D mm L mm 5KW 125A 200AH 1 4AWG 22 6 4 33 2 2 5 3 Nm 2...

Страница 8: ...ith IN and OUT markings Please do NOT mis connect input and output connectors WARNING All wiring must be performed by qualified person WARNING It s very important for system safety and efficient opera...

Страница 9: ...software in the CD Dry Contact Signal There is one dry contact 3A 250VAC available on the rear panel It could be used to deliver signal to connect external device based on different working mode Unit...

Страница 10: ...us and input output power information LED Indicators LED Indicator Messages Green Solid On Output is powered by utility in Line mode Flashing Output is powered by battery in battery mode Green Solid O...

Страница 11: ...mode it will present battery capacity as below table when unit is charging Status Battery voltage LCD Display Constant Current mode Constant Voltage mode 2V cell 4 bars will flash in turns 2 2 083V ce...

Страница 12: ...2 033 Load Information Indicates unit is overload Indicates the load level by 0 24 25 50 50 74 and 75 100 0 25 25 50 50 75 75 100 Mode Operation Information Indicates the load is supplied by utility p...

Страница 13: ...is from 48 0V to 58 4V for 48V model Each click increment 0 1V 06 Floating charging voltage Default setting 54V This program can be set up Setting range is from 48 0V to 58 4V for 48V model Each clic...

Страница 14: ...n default If selected no matter how users switch display screen it will automatically return to default display screen Input voltage output voltage after no button is pressed for 1 minute Stay at late...

Страница 15: ...arging power battery voltage output frequency and main CPU Version Selectable information LCD display Input voltage Output voltage Default Display Screen Input Voltage 220V output voltage 220V Input f...

Страница 16: ...low or not detected No output is supplied by the unit but it still can charge batteries Charging by utility No charging Fault mode Note Fault mode Errors are caused by errors inside circuit or extern...

Страница 17: ...Bus voltage is too high 09 Bus soft start failed 51 Over current or surge 52 Bus voltage is too low 53 Inverter soft start failed 55 Over DC voltage in AC output 56 Battery connection is open 57 Curr...

Страница 18: ...nsfer Time 10ms typical Transfer time may be longer than specified figure when the unit is operating in parallel system Table 2 Inverter Mode Specifications INVERTER MODEL 5KW Rated Output Power 5KVA...

Страница 19: ...Step Charging Curve Time Battery Voltage per cell Charging Current 100 50 Bulk Constant Current Absorption Constant Voltage Maintenance Floating Current Voltage T1 T1 10 T0 minimum 10mins maximum 8hrs...

Страница 20: ...inuously and red LED is on Fault code 07 Overload error The inverter is overload 110 and time is up Reduce the connected load by switching off some equipment Fault code 05 Output short circuited Check...

Страница 21: ...r each inverter Model Wire Size Ring Terminal Torque value Cable mm2 Dimensions D mm L mm 5KW 1 4AWG 22 6 4 33 2 2 3 Nm 2 8AWG 14 6 4 29 2 WARNING Be sure the length of all battery cables is the same...

Страница 22: ...d to use 50A breaker for each unit in parallel system and a breaker should be installed for each inverter in the AC input Note 2 In three phase parallel system you can use one 4 pole breaker The accep...

Страница 23: ...21 Communication Connection Three inverters in parallel Power Connection Communication Connection Four inverters in parallel Power Connection...

Страница 24: ...22 Communication Connection Five inverters in parallel Power Connection Communication Connection Six inverters in parallel Power Connection Communication Connection...

Страница 25: ...e Power Connection Communication Connection Four inverters in one phase and one inverter for the other two phases Power Connection Note It s up to customer s demand to pick 4 inverters in any phase P1...

Страница 26: ...two inverters in second phase and one inverter for the third phase Power Connection Communication Connection Three inverters in one phase and only one inverter for the remaining two phases Power Conn...

Страница 27: ...o inverters in two phases and only one inverter for the remaining phase Power Connection Communication Connection Two inverters in one phase and only one inverter for the remaining phases Power Connec...

Страница 28: ...ication Connection One inverter in each phase Power Connection Communication Connection WARNING Do not connect the sharing cable between the inverters in different phases Otherwise it may damage the i...

Страница 29: ...ame phase Do NOT connect current sharing cable between units in different phases Besides power saving function will be automatically disabled Parallel L1 phase L2 phase L3 phase Fault code display Fau...

Страница 30: ...s necessary to turn off switch when setting LCD program Otherwise the setting cannot be programmed Step 3 Turn on all units sequentially LCD display in L1 phase unit LCD display in L2 phase unit LCD d...

Страница 31: ...e contact your installer 81 Host data loss 82 Synchronization data loss 83 The battery voltage of each inverter is not the same 1 Make sure all inverters share the same groups of batteries 2 Remove al...

Страница 32: ...Ah min 5KW 400 613 1288 800 268 613 1200 158 402 1600 111 271 2000 90 215 2400 76 182 2800 65 141 3200 50 112 3600 44 100 4000 40 90 5000 30 70 Note Backup time depends on the quality of the battery a...

Отзывы: