18
If self-defined is selected in program 14, this program can be
set up. Setting range is from 12.0V to 15.3V for 12Vdc model
and 24.0V to 30.6V for 24Vdc model.
Increment of each click is 0.1V.
19
Low DC cut off battery
voltage setting
12V model default setting: 10.2V
24V model default setting: 20.4V
If self-defined is selected in program 14, this program can be
set up. Setting range is from 10.2V to 12.0V for 12Vdc model
and 20.4V to 24V for 24Vdc model. Increment of each click is
0.1V. Low DC cut-off voltage will be fixed to setting value no
matter what percentage of load is connected.
20
Setting voltage point back
to utility source when
selecting “SBU priority” or
“Solar first” in program 01.
Available options for 12V models:
11.0V
11.3V
11.5V (default) 11.8V
12.0V
12.3V
12.5V
12.8V
Available options for 24V models:
22.0V
22.5V
23.0V (default)
23.5V
24.0V
24.5V