Testing extension cables, cable reels and multi-plugs
• Connect the IEC power cable (from GT-6000 v2 kit), to the IEC low - power
connector, IEC 60320 C14, (10).
• Connect extension cable to the test socket (1) and to the safety plug on
the IEC low-power cable.
• By pressing the button (2) automatic test (protection class 1) will start, R
PE
will be first measured.
• The rest of testing is the same as described above for testing of IEC power
cable.
Testing three-phase cable
• Connect the three-phase cable to the test socket (1), using the optional
passive measurement adapter.
• Insert the 4 mm safety connector of the test lead with alligator clip into the
4 mm safety socket (9) and connection to the PE on CEE connector of the
tested 3-phase cable.
• By pressing the button (2) automatic test (R
PE
, R
ISO
and I
EA
) will start.
I
PE
I
B
Phase
3