Cayenne

®

Medium-Duty Thermostatic Flat Top Griddles – Conversion to LP Gas Installation Instructions

3

TEST THE EQUIPMENT

Check the pressure of the incoming gas line

Before supplying gas to the regulator, check the pressure of the
incoming gas line.

The regulator can withstand a maximum pressure of 14" WC (1/2 PSI).
If the line pressure is beyond this limit, a step-down regulator will be
required. The arrow on the regulator body shows gas flow direction and
should point toward the appliance.

Check for gas leaks

NOTICE: Matches, candle flame, or any other potential source of

ignition shall not be used for this purpose.

1. Turn the knob for the main burner(s) to the OFF position.
2. Remove the main burner control knob(s).

3. Use a flathead screwdriver to remove the screws on the front panel.

Remove the front panel to access the pilot burner control valve(s).

4. Locate the pilot burner control valves for the pilot lights and turn

them OFF by turning the small forward-facing screw clockwise until
tight.

5. Connect the equipment to the gas supply.

6. Apply soapy water to each connection.

7. Turn ON the main supply valve.

8. Look for bubbles at the connections.

9. Adjust the connections as needed.

Light the pilot burners

1. Wait 5 minutes to allow any gas to dissipate.
2. To light the pilot burners, hold a flame source over the desired pilot

burner while slowly turning its control valve screw
counterclockwise, adjusting the flame to the desired intensity.
Repeat for all pilot burners.

Test the main burners

After lighting all of the pilot burners, ensure that each main burner
functions correctly.

Reassemble the equipment

Allow the burners and surrounding surfaces to cool before
reassembling the equipment.

Affix the labels

1. Affix the Rating Plate, supplied in the kit, adjacent to the original on

the rear of the griddle.

2. Fill in the details required on the Installation Plate, supplied in the kit,

and affix to the rear of the griddle.

3. Affix the Warning Label, supplied in the kit, near the regulator.

The  Vollrath Company,  LLC 

Sheboygan,WIUSA 

1-888-882-6845

®

Griddle, Gas, Flat Top,  MD, Thermostatic  24" 

Item: 40722 

Model: FTA1024 

Converted for  use  with  LP  (propane) Gas 

Orifice Size:  #53 Drill

5PUBM

Input: 

 000 BTU 

Conversion Kit: 

X

FTA1001LP 

Manifold Pressure: 10" WC 

Max. Pressure : 14" WC 
Made in China 

Fabrique aux La China 
Hecho en China 

Intended for other than houshold use  - Non destine a l'usage  domestique 

MH62943

ANS Z83.11
CSA 1.8 - 2016
Food Service Equip.

CONVERSION BY QUALIFIED SERVICE AGENCY 

THIS APPLIANCE WAS CONVERTED ON: 

day  

month  

year 

to LPG gas with KIT #:   

by:   C ompany     

Address:  

Which accepts the responsibility that this conversion has been properly  made 

LPG

GPL

CLEARANCES

ESPACES LIBRES

FOR LP GAS WHEN EQUIPPED WITH NO. 53 DRILL SIZE ORIFICE

POUR LP GAZ LORSQU’ ÉQUIPÉ ’AVEC UNE OUVERTURE
DE TAILLE DE MÈCHE NO. 53

INCH W.C.

MAN.PRESS.

PRESS. MAN.

BACK
ARRIERE

6”

RT SIDE
COTE DROIT

6”

LT SIDE
COTE GAUCHE

6”

DOIT ETRE UTILISE SEULEMENT DAS DES LOCAUX NON INFLAMMABLES

FOR USE IN NON COMBUSTIBLE LOCATIONS ONLY

FOR YOUR SAFETY REFER TO INSTALLATION INSTRUCTIONS FOR CONVERSION PROCEDURES

10.0

TOTAL TOTAL
BTU/HR

56,000

TOTAL D'ENTRÉE
BTU/H

Содержание 40722

Страница 1: ...for testing connections WARNING CAUTION WARNING Fire Injury Death Hazard This conversion kit shall be installed by a qualified service agent in accordance with the manufacturer s instructions and all...

Страница 2: ...at elevations above 2000 ft 600 m equipment ratings shall be reduced at the rate of 4 percent for each 1000 ft 300 m above sea level when calculating how to select appropriately sized orifices 1 Apply...

Страница 3: ...pilot burners Test the main burners After lighting all of the pilot burners ensure that each main burner functions correctly Reassemble the equipment Allow the burners and surrounding surfaces to coo...

Страница 4: ...53081 3201 U S A Main Tel 800 624 2051 or 920 457 4851 Main Fax 800 752 5620 or 920 459 6573 Customer Service 800 628 0830 Canada Customer Service 800 695 8560 Technical Services techservicereps voll...

Страница 5: ...NT ATTENTION AVERTISSEMENT Risque de d part de feu blessures ou danger de mort Ce kit de conversion devra tre install par un agent de maintenance qualifi conform ment aux instructions du fabricant et...

Страница 6: ...de 2 000 pi 600 m Pour un fonctionnement plus de 2 000 pi 600 m les valeurs nominales des appareils seront r duites raison de 4 pour 1 000 pi 300 m au dessus du niveau de la mer lors du calcul du mod...

Страница 7: ...aiguilles d une montre pour ajuster la flamme l intensit voulue Reprenez pour tous les br leurs de veilleuse Test des br leurs principaux Apr s avoir allum tous les br leurs de veilleuse assurez vous...

Страница 8: ...boygan Wi 53081 3201 tats Unis Standard 800 624 2051 ou 920 457 4851 T l copieur 800 752 5620 ou 920 459 6573 Service client le 800 628 0830 Service client le Canada 800 695 8560 Services techniques t...

Страница 9: ...ADVERTENCIA PRECAUCI N ADVERTENCIA Peligro de incendio lesiones o la muerte Este juego de conversi n debe ser instalado por un agente de servicio calificado de conformidad con las instrucciones del f...

Страница 10: ...to en altitudes de m s de 2000 pies 610 m deben reducirse las clasificaciones nominales de los equipos a una tasa del 4 por ciento por cada 1000 pies 300 m sobre el nivel del mar al calcular c mo sele...

Страница 11: ...en sentido antihorario ajustando la llama a la intensidad deseada Repita este procedimiento en todos los quemadores piloto Pruebe los quemadores principales Tras encender todos los quemadores piloto c...

Страница 12: ...E UU Tel principal 800 624 2051 920 457 4851 Fax principal 800 752 5620 920 459 6573 Servicio al cliente 800 628 0830 Servicio al cliente en Canad 800 695 8560 Servicios de asistencia t cnica techserv...

Отзывы: