background image

WARNING:

1.  Opening the unit without prior permission 

from Vollara will void its warranty coverage. 
Contact Vollara at 1.800.989.2299 if you 
have any questions.

2.   Apply this unit to 120V AC 60Hz, single phase 

load only.

3.   The unit must be mounted vertically, in a dry 

location, using the four provided mounting clips.

4.   WARNING! THIS UNIT MUST BE INSTALLED 

BY A LICENSED ELECTRICIAN (IN 
COMPLIANCE WITH LOCAL ELECTRICAL 
CODES). FAILURE TO DO SO COULD 
RESULT IN DEATH OR SERIOUS INJURY.

5.  

IMPORTANT! 

This unit must be connected 

directly to a dedicated circuit breaker. Do not, 
under any circumstances, hard-wire install 
without a dedicated breaker!

6.   Proper installation of this unit requires 

the dedicated breakers (two (2) single 
pole, 20 amp breakers required) to be 
installed in breaker positions 1 and 2 (upper 
most positions in the breaker panel).  
NOTE: If these positions are already in 
use in your breaker panel, the electrician 
must relocate the circuits that currently 
occupy these positions (positions 1 and 
2) to open positions located lower in the 
breaker panel.  FAILURE TO FOLLOW THIS 
INSTALLATION PROCEDURE WILL VOID 
YOUR WARRANTY ! 

YOU WILL NEED:

1.   Two (2) dedicated, single pole, 20 amp circuit 

breakers.

2.   Appropriate tools including conduit.

3.   A licensed electrician for installation.

MOUNTING THE STEADYPOWER FLUSH-

MOUNT (ECP240R)

WARNING! THIS UNIT MUST BE INSTALLED BY 
A LICENSED ELECTRICIAN (IN COMPLIANCE 
WITH LOCAL ELECTRICAL CODES). FAILURE 
TO DO SO COULD RESULT IN DEATH OR 
SERIOUS INJURY. DE-ENERGIZE POWER PANEL 
(WE RECOMMEND TURNING OFF THE MAIN 
POWER BREAKER) PRIOR TO BEGINNING THIS 
PROCEDURE.

NOTE: 

For surface mounted applications, you will 

need a surface mounting adapter plate. See your 
Vollara Independent Business Owner for more 
information.

1.   Inspect the exterior of the unit to ensure that it 

has not been damaged in transit. Ensure that 
the front label/overlay is still intact, and that 
the cables protruding from the unit have not 
been damaged.

2.   Place the back of the Flushmount Box against 

wall where the unit is to be installed and trace 
around its outside edge. Cut drywall along 
traced line (dimension of traced area should 
be approximately 4.866” wide by 8.250” high). 

3.   Run conduit (according to code) between the 

conduit connector on the box and the power 
panel, and feed the connection cables through 
the conduit into the power panel.

4.  Secure the four (4) clips to the mounting box 

and tighten screws to tightly fit.

5.  Screw Cover Plate onto unit.

INSTALLATION PROCEDURES:

1.   De-energize power panel prior to connection 

of the Steady Power unit (we recommend 
turning off the Main Power Breaker). 

2.  Install the two (2) single pole, 20 amp circuit 

breakers into circuit positions 1 and 2  (see 
item 6 in “Warning Section” above) of the 
circuit panel. 

3.  Connect the RED wire (L1) to the circuit 

breaker located in position 1, the BLACK wire 
(L2) to the circuit breaker located in position 2, 
the GREEN with yellow stripe wire (Ground) to  
the ground bus, and the WHITE wire (Neutral) 
to the neutral bus, as shown in the diagram  
on page 3.  

 

Отзывы: