background image

 

Instruction Manual

Voith Turbo

 

Way Valve WSR-D16212

 

 

 

 

2003 / 07  aie 

Voith Turbo GmbH & Co. KG 

Page: 20 / 24

918 3626 018870 en 

D – 74564 Crailsheim 

Version: 3.0

 
 

7.3 Troubleshooting 

 

  Troubleshooting must only be performed in a non-hazardous atmosphere.  

 

 

  Prior to starting the work, make sure that the way valve was installed electrically and 

hydraulically according to the information provided in Chapter 5 and properly 
commissioned according to the information provided in Chapter 6. 

 
 

Malfunction

 

Possible cause(s) 

Remedy 

The piston rod 
shows temporary 
stroke variations. 

Air pockets and/or lack of 
damping 

De-aerate the way valve as per Chapter 6.1. 

 

Precondition: 
Disconnect external setpoint and connect
setpoint source directly to the way valve. 

Electrical fault on the 
connecting cable and/or 
vibration of the master 
controller 

Establish precondition and enter a constant
setpoint. If a stroke variation does no longer
occur, check the connecting line and/or the
master controller for malfunctions and/or
defects. 

Proportional gain set too high Establish precondition and realize setpoint step-

changes. If this causes periodic stroke
variations, readjust the gain. See Chapter 6.2.3.

The piston rod 
shows periodical 
stroke variations 

There is mechanical friction 
in the slide valve. 

Establish precondition. Enter setpoint w 0 8 mm
for t = 30 sec. Then increase the setpoint in one
step to 8.5 mA and keep it constant for 30 sec. If
the stroke varies in one of the two phases,
ingress of dirt into the slide valve may be the
cause. Open slide valve and clean interior parts.
In case of damage to the control edges and
surfaces, completely replace the way valve. 

Piston rod shows 
sporadic stroke 
variations 

Connecting fault and/or 
defective electric lines 

Connect setpoint source directly to the way 
valve. If this remedies the malfunction, check the 
electric line. 

 

Defect in the Voith control 
magnet 

Connect setpoint source directly to the way 
valve. If malfunctioning still continues, replace 
the control magnet. 

Содержание WSR-D16212

Страница 1: ...GmbH Co KG Page 1 24 918 3626 018870 en D 74564 Crailsheim Version 3 0 7 Way Valve Type WSR D16212 Instruction Manual Version 3 0 ATTENTION Please make sure to read this instruction manual prior to tr...

Страница 2: ...oup Electronic Drive Systems Direct dial 49 7951 32 470 Direct fax 49 7951 32 605 Email turbinenstelltechnik voith com Address for deliveries of goods Voith Turbo GmbH Co KG aie Dept Voithstra e 1 D 7...

Страница 3: ...ng Storage and Transportation 11 5 Installation 12 5 1 Mounting 12 5 2 Hydraulic connection 13 5 3 Electrical connection 13 6 Commissioning 14 6 1 Test run 14 6 2 Parameter setting 15 6 2 1 Setting th...

Страница 4: ...ta Supply pressure P Nominal pressure 90 bar Maximum pressure 120 bar Return pressure T 0 05 0 2 bar Flow rate at P 20bar P A B T 45 l min Operating medium Type Hydraulic oil to DIN 51524 Turbine oil...

Страница 5: ...Chapter 10 Control Parameters Setpoint w for stroke 0 100 w 4 0 20 0 load 100 mA Actual value input for stroke 0 100 20 4 load 332 mA Actual value remote indication for stroke 0 100 4 20 load 400 max...

Страница 6: ...e serves to transform an electric position set signal e g 4 20 mA into a flow rate variable in direction and size This allows for example remote controlled infinitely variable adjustment of a hydrauli...

Страница 7: ...switch off the hydraulic and electric auxiliary energy Electric components are integrated in the way valve which may be destroyed e g during electric welding near the way valve Prior to performing el...

Страница 8: ...n the General Terms and Conditions of Sale for Industrial Engineering of Voith Turbo GmbH Co KG Crailsheim shall apply Warranty claims are excluded if these are due to one or several of the following...

Страница 9: ...Sectional view of way valve The way valve comprises the main functional units 1 Control magnet P input pressure 2 Tappet for power transmission A B outputs 3 Potentiometers X0 X1 KPU KP T tank return...

Страница 10: ...positioner The actuating variable hereby generated acts as setpoint for the subordinate magnetic force controller A power range for FMag is allocated the actuating variable range via parameters F0 and...

Страница 11: ...delivery the inner parts of the way valve which are not surface coated are moistened with preservation oil Within Europe this preservation is sufficient as corrosion protection for about 8 months pro...

Страница 12: ...valve Cleanliness is imperative during both installation and connection Prevent any impurities dust metal chips etc from getting into the interior of the way valve or into the piping system Any such i...

Страница 13: ...removing the screw plugs Collect the oil in a suitable container and dispose it off properly Do not use fibrous or hardening sealing compounds such as hemp or mastic to seal the connections and pipe u...

Страница 14: ...d the de aeration process Prior to the test run please ensure that the pipes and the hydraulic system have been cleaned The operating medium must correspond to the cleanliness grade stated in Chapter...

Страница 15: ...he piston is started in the actuator Preset setpoint step change in closing direction e g 18 6 mA Check the step response and if necessary optimize with potentiometer KP and TD See Chapter 6 2 3 Durin...

Страница 16: ...deviation between the setpoint and the actual value remote indication a magnetic force offset is adjusted by potentiometer FM This offset is selected so that the control deviation is zero at setpoint...

Страница 17: ...of 4 mA even at thermal linear expansion or drifting of a signal the stroke may also be adjusted at a setpoint of e g 4 5 mA Effective direction of X0 The piston moves towards 100 by turning the pote...

Страница 18: ...ertheless adjust the KP according to the procedure described above Advantage Better dynamic behavior in case of minor setpoint changes and lower deviation between the setpoint and the actual position...

Страница 19: ...by turning it counterclockwise and lock it by pushing in the circlip Move the piston of actuator from 0 to end position 100 Slowly adjust the manual operation know by turning it clockwise Observe the...

Страница 20: ...oes no longer occur check the connecting line and or the master controller for malfunctions and or defects Proportional gain set too high Establish precondition and realize setpoint step changes If th...

Страница 21: ...ecessary contact Voith Turbo Fuse blown The upstream fuse of the way valve responds or the maximum power consumption is being exceeded Defect in the Voith control magnet If the piston of the actuator...

Страница 22: ...meet the criteria as per Chapter 2 3 Maintenance intervals Maintenance work Routine inspection Check pipes pipe unions and connections on the way for leaks impurities and damage Remedy any leaks impur...

Страница 23: ...erformed by the operator s trained expert personnel in an appropriate workshop or by Voith personnel at the Voith workshop see Chapter 2 3 Inspection works after another 60 000 operating hours 7 years...

Страница 24: ...n disassembling the hydraulic connection on the way valve Disconnect the 24 V DC power supply and remove the lines Remove the piping This may result in larger oil quantities leaking out Collect the oi...

Страница 25: ......

Отзывы: