8.
Installation Details
8.1 Wrench torque sheet for installation
Outside diameter
Torque
Additional tightening torque
mm N.cm N.cm
Ф
6.35 1500(153kgf.cm)
1600(163kgf.cm)
Ф
9.52 2500(255kgf.cm)
2600(265kgf.cm)
Ф
12.7 3500(357kgf.cm)
3600(367kgf.cm)
8.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Rated current of appliance
Nominal cross-sectional area (mm²)
>3 and
≤
6 0.75
>6 and
≤
10 1
>10 and
≤
16 1.5
>16 and
≤
25 2.5
The cable size and the current of the fuse or switch are determined by the maximum current indicated on the
nameplate which located on the side panel of the unit. Please refer to the nameplate before selecting the
cable, fuse and switch.
8.3 Pipe length and the elevation
Maximum piping length and height difference
1 drive 2
1 drive 3
1 drive 4
1 drive 5
Max. length for all rooms (m)
30 45 60 75
Max. length for one IU (m)
20 25 30 30
Max. height difference
between IU and OU (m)
OU higher than IU
10 10 10 10
OU lower than IU
15
15
15
15
Max. height difference between IUs (m)
10 10 10 10
Additional refrigerant charge
1 drive 2
1 drive 3
1 drive 4
1 drive 5
Chargeless pipe
length (m)
10 15 20 25
Additional
refrigerant charge
(g)
15 x (length for all
rooms - 10)
15 x (length for all
rooms - 15)
15 x (length for all
rooms - 20)
15 x (length for all
rooms - 25)
Caution:
Содержание ACP-18COFM50AECI
Страница 2: ......
Страница 10: ...4 Wiring Diagram ACP 18COFM50AECI ...
Страница 11: ...ACP 27COFM79AECI ACP 28COFM82AECI ...
Страница 12: ...ACP 41COFM123AECI ACP 36COFM105AECI ...
Страница 41: ...10 3 1 2 Indoor outdoor units communication error ...
Страница 48: ...10 3 2 2 Communication malfunction between IPM board and outdoor main board ODU E3 ...
Страница 51: ...10 3 2 5 High pressure protection ODU P1 For ACP 36COFM105AECI ACP 28COFM82AECI ACP 41COFM123AECI ...
Страница 63: ......
Страница 64: ...www VIVAX com ...