MCAC-UTSM-2008-04
Troubleshooting
Outdoor Units
41
3. Timer lamp flash at 5Hz
Timer lamp flash at 5Hz
Communication malfunction between indoor/outdoor units
Judge 3: Check whether the signal wiring between
the indoor and outdoor units is wrong polarity?
Connect the signal wiring correctly
Yes
No
Judge 4: Check whether the signal wiring between
the indoor and outdoor units is broken?
Yes
Replace the broken wiring
No
Judge 2: Check whether the signal wiring is shield
cable or whether the shield cable is earthing
Yes
No
Indoor or outdoor main board is broken, replace the
main board until the malfunction is disappear
Judge 1: Check whether the indoor unit power is on
Turn on the indoor unit power
No
Yes