7URXEOHVKRRWLQJ
Balance Refrigerant of the 3-way Valve
(Gas leakage)
• Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat.
(2) Connect the charge set to the 3-way valve’s
port.
– Leave the valve on the charge set closed.
– Connect the charge hose to the service port.
(3) Open the valve (Lo side) on the charge set and
discharge the refrigerant until the gauge indi-
cates 0 kg/cm
2
G.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not running
is higher than 1 kg/cm
2
G), discharge the refrig-
erant until the gauge indicates 0.5 to 1
kg/cm
2
G. if this is the case, it will not be neces-
sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will
also be discharged.
Lo
Open
Open
3-Way
valve
3-Way
valve
Gas side
CLOSE
OPEN
Outdoor unit
Liquid side
Indoor unit
Содержание ACP-09CH25GECI
Страница 1: ...ACP 09CH25GECI ACP 12CH35GECI Service manual ENG RoHS ...
Страница 2: ......
Страница 5: ...ACP 09CH25GECI ACP 09CH25GECI I ACP 12CH35GECI ACP 12CH35GECI I ...
Страница 6: ...ACP 09CH25GECI O ACP 12CH35GECI O ...
Страница 9: ... RQVWUXFWLRQ 9LHZV RQVWUXFWLRQ 9LHZV QGRRU 8QLW 8QLW PP ...
Страница 10: ...710 658 275 550 318 470 299 Model ACP 12CH35GECI O Model ACP 09CH25GECI O ...
Страница 32: ......
Страница 33: ...Models ACP 09CH25GECI I ACP 12CH35GECI I ...
Страница 34: ...is ACP 09CH25GECI I ACP 12CH35GECI I ...
Страница 35: ...Model ACP 09CH25GECI O ...
Страница 36: ...is ACP 09CH25GECI O ...
Страница 37: ...Model ACP 12CH35GECI O ...
Страница 38: ...is ACP 12CH35GECI O ...
Страница 67: ......
Страница 68: ......
Страница 69: ......