28
3. Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge indicates
0.05 to 0.1Mpa.
If the pressure when the air conditioner is not running is higher than 0.1Mpa, discharge the refrigerant
until the gauge indicates 0.05 to 0.1 Mpa. Discharge the refrigeration gradually; if it is discharged
suddenly, the refrigeration oil will be discharged.
6.11 Evacuation
Procedure:
1. Connect the vacuum pump to the charge set
’
s center hose.
2. Evacuation for approximately one hour.
Confirm that the gauge needle has moved toward -0.1 Mpa (-76 cmHg) [vacuum of 4 mmHg or less].
3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge
needle does not move (approximately 5 minutes after turning off the vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
文件使用
"pdfFactory Pro"
试用版本创建
www.fineprint.cn
Содержание ACP-09CH25AEI
Страница 2: ......
Страница 12: ...9 3 Dimension 3 1 Indoor Units For ACP 09CH25AEI ACP 12CH35AEI ACP 12CH35AECI models ...
Страница 15: ...12 4 Refrigerant Cycle Diagram PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Страница 17: ...14 ACP 18CH50AEI ACP 24CH70AEI PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Страница 18: ...15 ACP 09CH25AEI PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Страница 19: ...16 ACP 18CH50AEI PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Страница 20: ...17 ACP 09CH25AEI ACP 12CH35AEI ACP 12CH35AECI PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Страница 21: ...18 ACP 24CH70AEI PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Страница 43: ...40 Defrosting action For 9k 12k models For 18k 24k models PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Страница 52: ......
Страница 53: ......
Страница 54: ......