Scope
This manual is intended for the external control unit
OSE-C 2323 (230 V) or OSE-C 2324 (24V), in combina-
tion with 1-2 OSE- or 8k2 safety edges.
Description
The external control unit OSE-C 2323 / OSE-C 2324 has
been developed according to the requirements:
-
Safety category 3 (DIN EN ISO 13849-1)
-
Performance level d (DIN EN ISO 13849-1)
The device consequently can be utilized for automated
doors and gates in accordance to the European standards
EN 12453 and EN 12978.
Modus OSE-8k2
The control unit will monitor up to two optical or two 8k2
safety edges. The active mode “OSE” or “8k2” can be
changed with the help of a switch located at the lower
bottom part of the circuit board.
Output Relay Contacts
The contact of the redundant output-relay (terminals 33/34
“Edge”) stays open, if one of the two installed safety edg-
es is actuated. A differentiation between the two safety
edges is not possible.
Reverse contact
After the opening of the output relays, a NO-reverse con-
tact (terminals 23/24 “Rev”) will be closed for a short peri-
od to re-open the door. The time delay before the door
reverses can be set to 50 ms (“Fast”) or to 500ms (“Slow”)
This can be done by toggling the switch at the lower bot-
tom part of the ci
rcuit board (“Fast-Slow”). The contact
closes for abt. 0,5 s.
Ancillary Safety Switches
The external control unit will also monitor various other
stop-only switches, which are fitted on the door leaf, e.g.
slack-cable-switch or passage-door-interlock.
The opening of this chain of switches opens an NC out-
put-contact (terminals 13/14 "Safety").
Screw Terminals
For easy installation the unit is equipped with plug-in
screw-type terminals.