Visonic MCT-426 Скачать руководство пользователя страница 3

D-302151 MCT-426, MCT-427 Installation Instructions 

3.5 Mounting  

1

Mark and drill 2 holes in

the mounting surface.

Fasten the bracket to the

mounting surface with 2 screws.

2

Align bracket tabs with the

detector slots and rotate the detector

as shown. Pull the detector outward to

verify that it is securely attached.

BRACKET

DETECTOR

tab

(1 of 3)

 

Figure 4. 

Mounting

 

Notes 

1. A battery must be inserted into the detector before the detector 

can be mounted onto the bracket. 

2. 

Unauthorized removal of the unit from the bracket will initiate a 

tamper alert!

 

3.6 Test 

Enter the test mode by pressing the test button. In this mode, the 
detector will test smoke, heat and battery functions. If all functions are 
good, the red LED lights 0.5s, off 0.5s, the yellow LED lights 0.5s, off 
0.5s followed by a loud 3-beep alarm and the red LED flashes 
simultaneously. Otherwise, the detector produces the warning signals 
as detailed in Table 1. 

3.7 LED Transmission Procedure 

The yellow LED can be set to ON or OFF by pressing the 
Transmission LED (yellow) ON/OFF button (see Figure 3), as 
indicated in Table 2 below. 

Table

 

2. 

Interpreting the Transmission ON/OFF Button 

Transmission LED ON/OFF 
button (yellow) press

 

LED (yellow) Status during 
transmission

 

Press and release, flashes once

 

ON

 

Press and release, flashes twice

 

OFF  

 

4. SMOKE DETECTOR INSTALLATION OVERVIEW 

4.1 Where to Install Smoke Detectors 

In the USA, smoke detectors should be installed in accordance with 
the NFPA Standard 74 (National Fire Protection Association, 
Batterymarch Park, Quincy, MA 02169). In Canada, smoke detectors 
should be installed in accordance with 

CAN/ULC-S553 - Standard for 

the Installation of Smoke Alarms

. For complete coverage in 

residential units, smoke detectors should be installed in all rooms, 
halls, storage areas, basements and attics in each family living unit. 
Minimum coverage is one detector on each floor and one in each 
sleeping area and attics in each family living unit. For maximum 
protection, a smoke detector should be located outside primary 
sleeping areas or on each level of your home. Here are a few useful 
tips for you: 

 Install a smoke detector in the hallway outside every separate 

bedroom area, as in Figure 5. Two detectors are required in homes 
with two bedroom areas, as in Figure 6. 

 Install a smoke detector on every floor of a multi-floor home or 

apartment, as shown in Figure 7. 

  Install a minimum of two detectors in any household. 

  Install a smoke detector inside every bedroom. 

  Install smoke detectors at both ends of a bedroom hallway if the 

hallway is more than 12 meters (40 feet) long. 

 

 

Figure 5. 

Locations for Placing Smoke Detectors in a Single 

Residence with only One Sleeping Area

 

  Install a smoke detector inside every room where one sleeps with 

the door partly or completely closed, since smoke could be blocked 

by the closed door and a hallway alarm may not wake up the 

sleeper if the door is closed. 

 

Figure 6.

 Locations for Placing Smoke Detectors in Single-Floor 

Residence with More than One Sleeping Area. 

 

Figure 7. 

Placing Smoke Detectors in a Multi-Floor Residence 

  Install basement detectors at the bottom of the basement stairwell. 

  Install second-floor detectors at the top of the first-to-second floor 

stairwell. 

  Be sure no door or other obstruction blocks the path of smoke to 

the detector. 

  Install additional detectors in your living room, dining room, family 

room, attic, utility and storage rooms. 

 Install smoke detectors as close to the center of the ceiling as 

possible. If this is not practical, put the detector on the ceiling, at 

least 10 cm (4 inches) away from any wall or corner, as shown in 

Figure 8. 

  If ceiling mounting is not possible and wall mounting is permitted by 

your local and state codes, locate the detectors between 10 - 15 

cm (4 - 6 inches) from the ceiling, also see Figure 8. 

  If some of your rooms have sloped, peaked, or gabled ceilings, try 

to mount detectors 0.9 meter (3 feet) measured horizontally from 

the highest point of the ceiling as shown in Figure 9. 

Отзывы: