Visonic MCR-304 Скачать руководство пользователя страница 3

DE3174 

4.2 Mounting the Base in Place 

To install the cabinet, proceed as follows: 

A.

 Hold the base against the mounting surface and mark the 

points for drilling (see mounting holes in Figure 2).  

B. 

Drill the mounting holes and insert wall anchors if necessary. 

Enter the wires into the base through the wiring knockouts. 
Attach the base to the mounting surface with two long screws. 

C. 

Complete the wiring as described in Para. 4.3.  

4.3 Wiring 

(Figures 4 through 7)

  

A.

  Connect the relay 

N.C.

 (or 

N.O.

) and 

C

 terminals of the MCR- 

304 to the selected zone input of the control panel in use. 

 Note:

 If the control panel remote control zone input is defined as 

E.O.L.,

 use appropriate 

E.O.L. 

resistors (see Figure 4). 

 

Figure 4.

 Using E.O.L. Resistors in the Relay Output Circuit  

B.

 If you wish to separate between status alerts, connect each 

status outputs of the MCR-304 (

TAMP

LBT 

and 

TRB

) to a 

separate zone input of the control panel, as shown in Figure 5. 

 

12V

RELAY

N.C.

N.O.

C

MCR-304

TERMINAL

BLOCK

12 VDC

OUT

G

Z1

CONTROL PANEL

18

Ω

+Vcc

+Vcc

+Vcc

18

Ω

18

Ω

NOTE:

 

ALL THREE

STATUS OUTPUTS
ARE NORMALLY
OPEN. THEY PULL
TO GROUND UPON
OCCURRENCE
OF LOW BATTERY,
TAMPER AND
TROUBLE EVENTS,
RESPECTIVELY.

NOTE:

 

THESE

CONNECTIONS
ARE CORRECT

IF ZONE INPUTS
ARE DEFINED AS
NORMALLY OPEN

REMOTE CONTROL

ZONE INPUT

 

Figure 5.

 General Wiring Diagram 

C.

  If you prefer to use only one zone input for status alerts, 

connect all 3 status outputs of the MCR-304 to a single zone 
input of the control panel, as shown in Figures 6 (E.O.L. 
option) and 7 (relay option). 

12V

RELAY

N.C.

N.O.

C

MCR-304

TERMINAL

BLOCK

12 VDC

OUT

REMOTE CONTROL

ZONE INPUT

G

Z1

TROUBLE

ZONE INPUT

CONTROL PANEL

E.O.L.

G

Z2

 

Figure 6.

 Wiring All 3 Status Outputs to a Single E.O.L. Zone

 

 

12V

RELAY

N.C.

N.O.

C

MCR-304

TERMINAL

BLOCK

12 VDC

OUT

G

Z1

TROUBLE

ZONE INPUT

CONTROL PANEL

RELAY COIL

N.C.

C

G

Z2

REMOTE CONTROL

ZONE INPUT

 

Figure 7.

 Wiring All 3 Status Outputs to a Single N.C. Zone

 

4.4 Customizing Your Receiver 

After wiring, you must set the relay output operating mode in 

accordance with the requirements of your specific application. 

Note:

 The relay output of the MCR-304 may be used for remote 

control tasks such as opening / closing a garage door. 

The PULSE / TOGGLE jumper determines the operating mode of 

the MCR-304 output relay (Pulse or Toggle):  

 

PULSE MODE 

Upon reception of a valid transmission, the output 

relay pulls in for as long as the transmission is 

received, plus 3 seconds. The relay will drop out 

when the “pulse timer” completes its countdown. 

 

Note:

 If another valid transmission is received during countdown, 

the pulse timer will be automatically reset and a new countdown 

will begin. 

TOGGLE MODE 

The output relay changes state each time it receives 

a valid transmission. Upon entering a new state, the 

toggle circuit is inhibited for 3 seconds, to impose a 

3-second interval between states. 

 

 

Note:

 If another valid transmission is received during the 3-

second inhibit period, the inhibit timer will be automatically reset 

and a new 3-second period will begin. 

 

5. MISCELLANEOUS COMMENTS 

5.1 The Effect of Transmitter Type on 

Output Relay Function in the PULSE 

Mode 

U

pon receiving a signal from one or several restoral- reporting 

transmitters, the MCR-304 will energize its output relay and will 

keep it this way until all transmitters signals restore. 

Note:

 If the system includes

 

restoral reporting transmitters, it is 

not recommended to set the MCR-304 to the toggle mode.

 

5.2 The Effect of Transmitter Type on 

the TRB (Trouble) Output 

The MCR-304 makes a distinction between supervised and non-

supervised transmitters. 

Supervised transmitters transmit an “attendance message” at 

regular intervals. If such a transmitter fails to send this message 

on time, the MCR-304 will activate its TRB (trouble) output.  
On the other hand, failure to receive an attendance message 

from a transmitter identified as a non-supervised device will be 

ignored by the MCR-304.  

5.3 Product Limitations  

Visonic Ltd. wireless systems are very reliable and are tested to 

high standards. However, due to their low transmitting power and 

limited range (required by FCC and other regulatory authorities), 

there are some limitations to be considered: 

A.

 Receivers may be blocked by radio signals occurring on or 

near their operating frequencies. 

B.

  A receiver can only receive one transmitted signal at a time. 

C.

 Wireless equipment should be tested regularly to determine 

whether there are sources of interference and to protect 

against faults. 

Отзывы: