Visonic :67 Скачать руководство пользователя страница 2

2

DE3541U

Figure 3: Recommended Smoke Detector Protection for a

Multilevel Residence

 

E. Put a smoke detector inside every bedroom where

someone sleeps with the door closed. Smoke could be
blocked by the closed door, or the alarm may not wake the
sleeper if the door is closed.

F. Put detectors as close to the center of the ceiling as

possible. If this is not practical, put the detector on the
ceiling, but no closer than 10 cm (4 in.) to any wall or
corner (Fig. 4).

Figure 4: 

Recommended Smoke 

Alarm Mounting Locations

G. If wall mounting is permitted by your local and state codes, put

wall-mounted detectors between 10 and 15 cm (4 and 6
inches) from the ceiling ( Fig. 4).

H. Put smoke detectors at both ends of a bedroom hallway if

the hallway is more than 12 m (40 ft) long.

I.

Put basement alarms at the bottom of the basement
stairwell
.

J. Put second-floor alarms at the top of the first-to-second

floor stairwell, as long as no other door or other
obstruction blocks the path of smoke to the alarm.

Figure 5: 

Recommended Smoke 

Alarm Mounting Locations in

Rooms with Sloped, Gabled or Peaked Ceiling

K. In rooms with sloped, peaked, or gabled ceilings, mount

detectors 0.9 m (3 ft) measured horizontally from the
highest point of the ceiling ( Fig. 5).

 :KHUH 6PRNH 'HWHFWRUV 6KRXOG %H /RFDWHG

LQ RPHV DQG 59·V

In mobile homes and recreational vehicles built after about 1978
that were designed and insulated to be energy-efficient, smoke

detectors should be installed as described in the section above.
In older mobile homes and RV’s that have little or no insulation
compared to today’s standards, uninsulated metal outside walls
and roofs can transfer heat and cold from outdoors, making the
air right next to them hotter or colder than the rest of the inside
air. These layers of hotter or colder air can prevent smoke from
reaching a smoke alarm. Therefore, put smoke detectors in such
units only on inside walls, between 10 and 15 cm (4 and 6
inches) from the ceiling. If you are not sure about the insulation
level in your mobile home or RV, or if you notice that the walls or
ceilings are unusually hot or cold, put the alarm on an inside wall.
Minimum protection requires one alarm as close to the sleeping
area as possible. For better protection, put one detector in each
room, but first read Section 6 - “Where Smoke Detectors Should
Not be Put”.

 :KHUH 6PRNH 'HWHFWRUV 6KRXOG 1RW %H 3XW

Nuisance alarms are caused by placing alarms where they will
not operate properly. To avoid nuisance alarms, do not place
detectors:
A. In or near areas where combustion particles are normally

present such as kitchens; in garages where there are particles
of combustion in vehicle exhausts; near furnaces, hot water
heaters, or gas space heaters. Install detectors at least 6 m
(20 ft) away from kitchens and other areas where combustion
is normally present.

B. In air streams passing by kitchens. Figure 6 shows how a

detector can be exposed to combustion particles in normal air
movement paths, and how to correct this situation.

C. In damp or very humid areas, or next to bathrooms with

showers. The moisture in humid air can enter the sensing
chamber as water vapor, then cool and condense into droplets
that cause a nuisance alarm. Install alarms at least 1.5 m (5
ft) away from bathrooms.

D. In very cold or very hot environments, or in unheated buildings

or outdoor rooms, where the temperature can go below or
above the operating range of the detector. Temperature limits
for proper operation are 4° to 38°C (40° to 100°F).

E. In very dusty or dirty areas. Dust and dirt can build up on the

detector’s sensing chamber and make it overly sensitive, or
can block openings to the sensing chamber and keep the
detector from sensing smoke.

F. Near fresh air inlets or returns or excessively drafty areas. Air

conditioners, heaters, fans, and fresh air intakes and returns
can drive smoke away from smoke detectors, making the
detectors less effective.

Figure 6: 

Recommended Smoke 

Alarm Locations to Avoid Air

Streams with Combustion

G. In dead air spaces at the top of a peaked roof or in the

corners between ceilings and walls. Dead air may prevent
smoke from reaching a detector. See Figures 4 and 5 for
recommended mounting locations.

H. In insect-infested areas. If insects enter a detector’s sensing

chamber, they may cause a nuisance alarm. Get rid of the
bugs before installing detectors where bugs are a problem.

I.

Near fluorescent light fixtures. Electrical “noise” from nearby
fluorescent light fixtures may cause a nuisance alarm. Install
detectors at least 3 m (10 ft) away from such light fixtures.

Отзывы: