Final Inspec�on

Once the flue system has been installed, a final inspection should be carried out.
Particular a�ention should be paid to:

50mm clearance requirement to combustibles from Safety Vent AIR pipe

100mm clearance requirement to combustibles from stove pipe

150mm clearance from transi�on to ceiling (stove pipe to safety vent) requirements

Flue height requirements per AS/NZS 2918

Elbow support bracket kit

VF-3-60-246

Use of bends

45o Bends can be used on this flue system. Either the stove pipe flue or the VisionLINE safety vent
flue can be offset. A maximum of two (2) sets of 45o elbows can be used. A maximum of 1800mm in
total can be run at a 45o angle.
If you are offse�ing VisionLINE safety vent pipe, you MUST brace the offset appropriately. 2
VisionLINE braces must be used to support the flue. (See fig 7) Furthermore, the joins must be sealed
using VisionLINE clamp braces (See fig 7)

FIG 7

PAGE 6

Содержание Safety Vent AIR

Страница 1: ...Safety Vent AIR Instruc on Manual...

Страница 2: ...mic insula on with a density of 128 kg m air gap of 20 mm 20 mm Morgan Frax ceramic insula on 128 kg m and outer wall of 0 5 mm SS 304 stainless steel VisionLINE Stove Pipe AIR is a double layer pipe...

Страница 3: ...od Prepara on Before installa on planning is essen al for an efficient safe and cost effec ve installa on ONLY VisionLINE safety vent AIR and VL Stove Pipe parts can be used for installa on Improvised...

Страница 4: ...ucting any additional frame work If the roof cavity is used as usable living or storage space or has blown in insulation an a ic shield is recommended to ensure the 50mm clearance to the Safety Vent A...

Страница 5: ...t if you require smaller sections please contact your distributor Safety Vent pipe does not require securing screws or rivets once twist locked together however if connec ng mul ple sec ons together t...

Страница 6: ...ntake system a T piece sec on can be used Part number VF 3 60 090 as the final VL stove pipe sec on which can then be connected to the rear air inlet either by flex pipe not supplied or the VisionLINE...

Страница 7: ...eight requirements per AS NZS 2918 Elbow support bracket kit VF 3 60 246 Use of bends 45o Bends can be used on this flue system Either the stove pipe flue or the VisionLINE safety vent flue can be off...

Страница 8: ...60 002 AIR FLUE SUPPORT 1 9 VF 3 60 108 AIR FLUE STOVE PIPE TO SAFETY VENT TRANSITION 10 VF 3 60 110 AIR FLUE CEILING RING 80MM 11 VF 3 60 105 AIR FLUE STOVE PIPE 620 1080MM ADJUSTABLE 12 VF 3 60 104...

Страница 9: ...3 mm 148 5 Ceiling Ring VF 3 60 110 Flush spigot adapter 193 L 30 Adjustable Stove pipe 193 L 30 Stove pipe Part number Joined length Total length VF 3 60 100 220mm 250mm VF 3 60 102 470mm 500mm VF 3...

Отзывы: