Installation Guide 

Unitronics  

Power Supply 

The controller requires an external 24VDC power supply.  The permissible input voltage range is 
20.4-28.8VDC, with less than 10% ripple. 

 

A non-isolated power supply can be used if a 0V signal is connected to the chassis. 

You must use an external circuit protection device. 
Install an external circuit breaker. Guard against 
short-circuiting in external wiring. 
Double-check all wiring before turning on the power 
supply. 
Do not connect either the ‘Neutral or ‘Line’ signal of 
the 110/220VAC to device’s 0V pin. 
In the event of voltage fluctuations or non-conformity 
to voltage power supply specifications, connect the 
device to a regulated power supply. 
To avoid electromagnetic interference, earth the 
power supply as described on page 3.  

Communication Ports 

This series comprises 2 RS232/RS485 serial ports and a CANbus port.  

Turn off power before making communications connections. 

Caution

 

Signals are related to the controller’s 0V; the same 0V is used by the power supply. 
Always use the appropriate port adapters. 

Serial Communications

The serial ports are type RJ-11 and may be set to 

either

RS232 or RS485 via DIP switches, in 

accordance with to the table shown on page 7.  
Use RS232 to download programs from a PC, and to communicate with serial devices and 
applications, such as SCADA.   
Use RS485 to create a multi-drop network containing up to 32 devices. 

Caution 

The serial ports are isolated. If the controller is used with a non-isolated external device, 
avoid potential voltage that exceeds ± 10V. 

Pinouts 

The pinouts below show the signals between the adapter and port. 

RS232  

RS485** 

Controller 

Port 

Pin # 

Description 

 

Pin # 

Description 

1* DTR 

signal 

 

1

A signal (+) 

2

0V reference 

 

2

(RS232 signal) 

3

TXD signal 

 

3

(RS232 signal) 

4

RXD signal 

 

4

(RS232 signal) 

5

0V reference 

 

5

(RS232 signal) 

6* DSR 

signal 

 

6

B signal (-) 

 

Pin #1

*Standard programming cables do not provide connection points for pins 1 and 6. 
**When a port is adapted to RS485, Pin 1 (DTR) is used for signal A,  
  and Pin 6 (DSR) signal is used for signal B. 

Содержание OPLC V290

Страница 1: ...ules Plug into the back of the controller to provide an on board I O configuration I O Expansion Modules Via adapter use up to 8 I O Expansion Modules comprising up to 128 additional I Os Programming Write both the HMI and Ladder control application using VisiLogic freeware The Vision User Guide and the product s technical specification sheet contain additional information These documents are loca...

Страница 2: ...r property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging the system do not connect disconnect the device when power is on Environmental Considerations Do not install in areas with excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration in accordance with the stan...

Страница 3: ...Dimensions 2 If you mount the controller on a metal panel earth the power supply a Bore a hole to suit the NC6 32 screw supplied with the kit b Scrape panel paint away from the contact area to ensure a conductive connection c Drive the screw into the hole d Place the following hardware screw s shank in the order shown in the accompanying figure washer ring cable shoe second washer spring and nut N...

Страница 4: ... and I O Expansion Modules Installation instructions and other data may be found in the module s technical specification sheet Wiring General Do not touch live wires Unused pins should not be connected Ignoring this directive may damage the device Caution To avoid damaging the wire do not exceed a maximum torque of 0 5 N m 5 kgf cm Do not use tin solder or any substance on stripped wire that might...

Страница 5: ...ections Caution Signals are related to the controller s 0V the same 0V is used by the power supply Always use the appropriate port adapters Serial Communications The serial ports are type RJ 11 and may be set to either RS232 or RS485 via DIP switches in accordance with to the table shown on page 7 Use RS232 to download programs from a PC and to communicate with serial devices and applications such...

Страница 6: ...tons on the sides of the controller two on either side 2 Press the buttons and hold them down to open the locking mechanism 3 Gently rock the module from side to side easing the module from the controller Opening and Closing the Controller 1 Locate the slots on the sides of the controller 2 Open the controller by inserting a flat bladed screwdriver into the slots located on the side of the control...

Страница 7: ...even pressure on all 4 corners until you hear a distinct click The module is now installed Check that all sides and corners are correctly aligned RS232 RS485 DIP Switch Settings Switch Settings 1 2 3 4 5 6 RS232 ON ON ON OFF ON OFF RS485 OFF OFF OFF ON OFF ON RS485 with termination ON ON OFF ON OFF ON Default factory setting Causes the unit to function as an end unit in an RS485 network ...

Страница 8: ... all applicable laws at any time at its sole discretion and without notice to discontinue or change the features designs materials and other specifications of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or implied including but not limited to any i...

Отзывы: